2004-12-29 00:00:00**************** UNSAT*****************
  
 1)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS THESE ARE GOING TO BE
 "TOWNHOUSES" YET PLANS FOR ELECTRICAL
 IS
 SET UP FOR WHAT APPEARS TO BE RENTAL
 APARTMENTS???
 IF THESE ARE "TOWNHOUSE" UNITS,
 ELECTRICAL WILL BE REQUIRED TO
 COMPLETELY CHANGE TO INDIVIDUAL
 SERVICES
 TO EACH.
 PLEASE SEE BLDG REVIEW COMMENTS.
  
 2)NOTE: PLEASE SEE 225.31,225.32,225.36
 IF DETACHED BLDGS, MCB WILL BE REQUIRED
 AT EACH PANEL FOR UNITS.
 MEANS SHALL BE PROVIDED FOR
 DISCONNECTING ALL UNGROUNDED CONDUCTORS
 THAT SUPPLY OR PASS THROUGH THE
 BUILDING
 OR STRUCTURE.
 THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF
 THE BUILDING OR STRUCTURE SERVED OR
 WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE
 DISCONNECTING
 MEANS SHALL BE AT A READILY ACCESSIBLE
 LOCATION NEAREST THE POINT OF ENTRANCE
 OF THE CONDUCTORS.
  
 3)NOTE: PLEASE SEE 225.36 THE
 DISCONNECTING MEANS SPECIFIED IN 225.31
 SHALL BE SUITABLE FOR USE AS SERVICE
 EQUIPMENT
  
 4)NOTE: PLEASE ALSO SEE 225.33 AND 34
 THE DISCONNECTING MEANS FOR EACH SUPPLY
 PERMITTED BY 225.30 SHALL CONSIST OF
 NOT
 MORE THAN SIX SWITCHES OR SIX CIRCUIT
 BREAKERS MOUNTED IN A SINGLE ENCLOSURE,
 IN A GROUP OF SEPARATE ENCLOSURES, OR
 IN
 OR ON A SWITCHBOARD. THERE SHALL BE NO
 MORE THAN SIX DISCONNECTS PER SUPPLY
 GROUPED IN ANY ONE LOCATION.THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN 225.33
 SHALL BE GROUPED. EACH DISCONNECT SHALL
 BE MARKED TO INDICATE THE LOAD SERVED.
  
 5)NOTE: PLEASE SEE GROUNDING AT
 DETACHED
 BLDGS PER 250.32
  
 6)NOTE: PLEASE SEE HP IS SHOWN AS MLO.
 PLEASE SEE ABOVE COMMENTS FOR 225.31
 ETC.
  
 7)NOTE: PLEASE SEE PANEL "H" IS SHOWN
 FED WITH 200A OCP WITH A 165A LOAD
 HOWEVER, THE CONDUCTORS SHOWN (1/0'S)
 ARE ONLY RATED FOR 150A'SPER 310.16,
 240.4B.
  
 8)NOTE: PLEASE SEE E-1, CONDUIT FEED IS
 NOT SHOWN FOR PANEL "H".
  
 9)NOTE: PLEASE SEE PANEL SCHEDULE AND
 LOAD CALCULATIONS MENTIONS A UNIT "C",
 HOWEVER, PLANS SUBMITTED DO NOT
 INDICATE
 A UNIT "C"??
  
 10)NOTE: PLEASE SEE DINING RM RECEPTS
 ARE REQUIRED TO BE ON A 20A #12
 CIRCUIT
 PER 210.52B1,210.11C1
 SOME SHOWN ON WITH LIV RM CIRCUIT.
  
 11)NOTE:: PLEASE SEE UNIT "B1" WITH
 FLEX
 RM. THIS ROOM BEING AN ADAPTABLE
 SLEEPING RM WILL BE REQUIRED TO AHVE A
 SD ALONG WITH ARC FAULT PROTECTION.
 NFPA-72 8-1.4.1.6.2, 210.12
  
 12)NOTE: PLEASE SUBMIT MANUFACTURE
 SPECS
 FOR TANKLESS WATER HEATERS SHOWING A
 LISTING FROM A NRTL.
 PLEASE SEE PANEL "B", THIS SHOWS OCP
 FOR
 THE 16KW UNIT AS 70A? PLEASE SEE PANEL
 "A" IS SHOWN AS 90A.
 PLEASE SEE 422.11F1, ELECTRIC HEATING
 APPLIANCES EMPLOYING RESISTANCE-TYPE
 HEATING ELEMENTS RATED MORE THAN 48
 AMPERES, OTHER THAN HOUSEHOLD
 APPLIANCES
 WITH SURFACE HEATING ELEMENTS COVERED
 BY
 422.11(B), AND COMMERCIAL-TYPE HEATING
 APPLIANCES COVERED BY 422.11(D), SHALL
 HAVE THE HEATING ELEMENTS SUBDIVIDED.
 EACH SUBDIVIDED LOAD SHALL NOT EXCEED
 48
 AMPERES AND SHALL BE PROTECTED AT NOT
 MORE THAN 60 AMPERES.
  
 13)NOTE: PLEASE SEE GDO SHOWN ON GEN
 BRANCH CIRCUIT WITH GARAGE LTS/RECEPTS.
 THIS IS NOT PERMITTED PER 430.32,430.42
 ETC WITH LOAD ON GDO SHOWN.
  
 14)NOTE: PLEASE SUBMIT COMPLETE
 WIND-LOADCALCS ETC FOR ALL SITE
 LIGHTING POLES AND FIXTURES. THESE MUST
 MEET FBC 140MPH.
 PLEASE SEE PLANS DO NOT INDICATE
 WHEATHER OR NOT ANY AFTER DUSK SWIMMING
 WILL TAKE PLACE?
 IF SWIMMING IS ONLY FROM DAWN TO DUSK ,
 PLEASE PLACE NOTE ON PLANS FOR THIS
 TIME
 OF SWIMMING ONLY.
 IF SWIMMING WILL TAKE PLACE AFTER DUSK,
 PLEASE SUBMIT SIGNED AND SEALED
 PHOTOMETRICS TO THE PALM BEACH COUNTY
 HEALTH DEPT FOR REVIEW AND STAMPING.
 PLANS MUST HAVE EITHER.
  
 15)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FS 481.219 FOR THE REQUIRED CERTIFICATE
 OF AUTHORIZATION NUMBER TO BE PRINTED
 ON
 TITLE BLOCK FOR ARCHITECTUAL FIRM. THIS
 COMMENT DOES NOT APPLY TO ENGINEERING
 FIRM AS CA # IS SHOWN.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S)
  
 16)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 THIS IS A COMMON TEXT NOTE: PLEASE SEE
 MISSING SD ON SECOND FLR.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW