| Date |
Text |
| 2004-12-29 00:00:00 | **************** UNSAT***************** |
| | |
| | 1)NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS THESE ARE GOING TO BE |
| | "TOWNHOUSES" YET PLANS FOR ELECTRICAL |
| | IS |
| | SET UP FOR WHAT APPEARS TO BE RENTAL |
| | APARTMENTS??? |
| | IF THESE ARE "TOWNHOUSE" UNITS, |
| | ELECTRICAL WILL BE REQUIRED TO |
| | COMPLETELY CHANGE TO INDIVIDUAL |
| | SERVICES |
| | TO EACH. |
| | PLEASE SEE BLDG REVIEW COMMENTS. |
| | |
| | 2)NOTE: PLEASE SEE 225.31,225.32,225.36 |
| | IF DETACHED BLDGS, MCB WILL BE REQUIRED |
| | AT EACH PANEL FOR UNITS. |
| | MEANS SHALL BE PROVIDED FOR |
| | DISCONNECTING ALL UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE |
| | BUILDING |
| | OR STRUCTURE. |
| | THE DISCONNECTING MEANS SHALL BE |
| | INSTALLED EITHER INSIDE OR OUTSIDE OF |
| | THE BUILDING OR STRUCTURE SERVED OR |
| | WHERE THE CONDUCTORS PASS THROUGH THE |
| | BUILDING OR STRUCTURE. THE |
| | DISCONNECTING |
| | MEANS SHALL BE AT A READILY ACCESSIBLE |
| | LOCATION NEAREST THE POINT OF ENTRANCE |
| | OF THE CONDUCTORS. |
| | |
| | 3)NOTE: PLEASE SEE 225.36 THE |
| | DISCONNECTING MEANS SPECIFIED IN 225.31 |
| | SHALL BE SUITABLE FOR USE AS SERVICE |
| | EQUIPMENT |
| | |
| | 4)NOTE: PLEASE ALSO SEE 225.33 AND 34 |
| | THE DISCONNECTING MEANS FOR EACH SUPPLY |
| | PERMITTED BY 225.30 SHALL CONSIST OF |
| | NOT |
| | MORE THAN SIX SWITCHES OR SIX CIRCUIT |
| | BREAKERS MOUNTED IN A SINGLE ENCLOSURE, |
| | IN A GROUP OF SEPARATE ENCLOSURES, OR |
| | IN |
| | OR ON A SWITCHBOARD. THERE SHALL BE NO |
| | MORE THAN SIX DISCONNECTS PER SUPPLY |
| | GROUPED IN ANY ONE LOCATION.THE TWO TO |
| | SIX DISCONNECTS AS PERMITTED IN 225.33 |
| | SHALL BE GROUPED. EACH DISCONNECT SHALL |
| | BE MARKED TO INDICATE THE LOAD SERVED. |
| | |
| | 5)NOTE: PLEASE SEE GROUNDING AT |
| | DETACHED |
| | BLDGS PER 250.32 |
| | |
| | 6)NOTE: PLEASE SEE HP IS SHOWN AS MLO. |
| | PLEASE SEE ABOVE COMMENTS FOR 225.31 |
| | ETC. |
| | |
| | 7)NOTE: PLEASE SEE PANEL "H" IS SHOWN |
| | FED WITH 200A OCP WITH A 165A LOAD |
| | HOWEVER, THE CONDUCTORS SHOWN (1/0'S) |
| | ARE ONLY RATED FOR 150A'SPER 310.16, |
| | 240.4B. |
| | |
| | 8)NOTE: PLEASE SEE E-1, CONDUIT FEED IS |
| | NOT SHOWN FOR PANEL "H". |
| | |
| | 9)NOTE: PLEASE SEE PANEL SCHEDULE AND |
| | LOAD CALCULATIONS MENTIONS A UNIT "C", |
| | HOWEVER, PLANS SUBMITTED DO NOT |
| | INDICATE |
| | A UNIT "C"?? |
| | |
| | 10)NOTE: PLEASE SEE DINING RM RECEPTS |
| | ARE REQUIRED TO BE ON A 20A #12 |
| | CIRCUIT |
| | PER 210.52B1,210.11C1 |
| | SOME SHOWN ON WITH LIV RM CIRCUIT. |
| | |
| | 11)NOTE:: PLEASE SEE UNIT "B1" WITH |
| | FLEX |
| | RM. THIS ROOM BEING AN ADAPTABLE |
| | SLEEPING RM WILL BE REQUIRED TO AHVE A |
| | SD ALONG WITH ARC FAULT PROTECTION. |
| | NFPA-72 8-1.4.1.6.2, 210.12 |
| | |
| | 12)NOTE: PLEASE SUBMIT MANUFACTURE |
| | SPECS |
| | FOR TANKLESS WATER HEATERS SHOWING A |
| | LISTING FROM A NRTL. |
| | PLEASE SEE PANEL "B", THIS SHOWS OCP |
| | FOR |
| | THE 16KW UNIT AS 70A? PLEASE SEE PANEL |
| | "A" IS SHOWN AS 90A. |
| | PLEASE SEE 422.11F1, ELECTRIC HEATING |
| | APPLIANCES EMPLOYING RESISTANCE-TYPE |
| | HEATING ELEMENTS RATED MORE THAN 48 |
| | AMPERES, OTHER THAN HOUSEHOLD |
| | APPLIANCES |
| | WITH SURFACE HEATING ELEMENTS COVERED |
| | BY |
| | 422.11(B), AND COMMERCIAL-TYPE HEATING |
| | APPLIANCES COVERED BY 422.11(D), SHALL |
| | HAVE THE HEATING ELEMENTS SUBDIVIDED. |
| | EACH SUBDIVIDED LOAD SHALL NOT EXCEED |
| | 48 |
| | AMPERES AND SHALL BE PROTECTED AT NOT |
| | MORE THAN 60 AMPERES. |
| | |
| | 13)NOTE: PLEASE SEE GDO SHOWN ON GEN |
| | BRANCH CIRCUIT WITH GARAGE LTS/RECEPTS. |
| | THIS IS NOT PERMITTED PER 430.32,430.42 |
| | ETC WITH LOAD ON GDO SHOWN. |
| | |
| | 14)NOTE: PLEASE SUBMIT COMPLETE |
| | WIND-LOADCALCS ETC FOR ALL SITE |
| | LIGHTING POLES AND FIXTURES. THESE MUST |
| | MEET FBC 140MPH. |
| | PLEASE SEE PLANS DO NOT INDICATE |
| | WHEATHER OR NOT ANY AFTER DUSK SWIMMING |
| | WILL TAKE PLACE? |
| | IF SWIMMING IS ONLY FROM DAWN TO DUSK , |
| | PLEASE PLACE NOTE ON PLANS FOR THIS |
| | TIME |
| | OF SWIMMING ONLY. |
| | IF SWIMMING WILL TAKE PLACE AFTER DUSK, |
| | PLEASE SUBMIT SIGNED AND SEALED |
| | PHOTOMETRICS TO THE PALM BEACH COUNTY |
| | HEALTH DEPT FOR REVIEW AND STAMPING. |
| | PLANS MUST HAVE EITHER. |
| | |
| | 15)NOTE: PLEASE SEE FAC 61G1-16.004 AND |
| | FS 481.219 FOR THE REQUIRED CERTIFICATE |
| | OF AUTHORIZATION NUMBER TO BE PRINTED |
| | ON |
| | TITLE BLOCK FOR ARCHITECTUAL FIRM. THIS |
| | COMMENT DOES NOT APPLY TO ENGINEERING |
| | FIRM AS CA # IS SHOWN. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S) |
| | |
| | 16)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | THIS IS A COMMON TEXT NOTE: PLEASE SEE |
| | MISSING SD ON SECOND FLR. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |