Plan Review Notes
Plan Review Notes For Permit 04120942
Permit Number 04120942
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-13 00:00:00BUILDING PLAN REVIEW
 PERMIT:04120942
 ADD: 2010 PONCE DE LEON AV
 CONT: TAYCON CONSTRUCTION
 TEL: (561)718-3045
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL
 LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR
 SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THERE
 SEEMS TO BE A DISCREPANCY IN THE
 PROJECT
 BETWEEN THE OCCUPANCY CLASSIFICATION.
 PERMIT APPLICATIONS INDICATE 8-UNIT
 TOWNHOMES, WHEREAS IT WAS INPUT INTO
 THE
  
 COMPUTER AS CONDOMINIUM.
 A1.1.0 PROJECT DATA INDICATES A-2
 MULTIFAMILY/ CONDOMINIUM
 A2.1.1 CONSTRUCTION NOTES: GROUP R-3,
 8 SINGLE FAMILY DWELLING TOWNHOMES.
 PLEASE MAKE CORRECTIONS, IF THIS IS TO
 BE CONDOMINIUM PLEASE REMOVE ALL
 TERMINOLOGY TOWNHOMES OR TOWNHOUSES.
  
 THIS REVIEW WILL BE COMPLETED WITH THE
 OCCUPANCY REQUIREMENTS FOR THE GROUP
 R-2
 APARTMENTS & CONDOMINIUM REQUIREMENTS.
 TYPE V UNPROTECTED / SPRINKLERED.
  
 2)THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL
 BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE
 600
 BOUNDARY LINE REQUIREMENTS MAY BE
 DEEMED
 NOT APPLICABLE.
  
 3)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 4)FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
 CORRECT FORMS (3) NUMBER OF UNITS
  
 5) SHEET A1.1.0 INDICATES THAT THE BACK
 OF THE BUILDINGS ARE LOCATED 5'-8" AWAY
 FROM THE PROPERTY LINE.
 5A)TABLE 600 REQUIRES THE EXTERIOR
 WALLS
 TO BE A 2HR RATING WHEN OVER 3' FROM
 THE
 PROPERTY LINE TO 10'-0" AWAY. HAVE THE
 BLOCK MANUFACTURER PROVIDE THE
 EQUIVALENT THICKNESS FOR THEBLOCK,
 SEE
 709.3.1.
 5B) SINCE THE REAR WALLS ARE LESS THAN
 15'-0" FROM THE PROPERTY LINE(ALL
 FLOORS) ANDA R-2 OCCUPANCY,
 705.1.1.2
 SHALL REQUIRE OPENING PROTECTIVES FOR
 THE REAR OPENINGS.
  
 6) THE SAME SITUATION OCCURS ON THE
 FRONT OF THESE BUILDINGS. TABLE 600 SEE
 EXTERIOR WALLS BEARING OR NONBEARING
 REQUIRES 2HR RATED WALLS AND ASSUMED
 PROPERTY LINES.
 6A) PROVIDE BLOCK EQUIVALENT THICKNESS
 FOR A 2HR RATED BLOCK 709.3.1.
 6B) LESS THAN 15' FROM AND ASSUMED
 PROPERTY LINE REQUIRING OPENING
 PROTECTIVES.
 6C) TABLE 600 ISSUES FRONT OF BUILDING
 LOCATED 12.66' FROM ASSUMED PROPERTY
 LINE ALLOWS 20% OPENINGS PER FLOOR. THE
  
 FIRST FLOOR OVER THE 20% ALLOWABLE
 OPENINGS.
  
 7) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR
 OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL
 DESIGN
 OR METHODS OF CONSTRUCTION
  
 8) NOTE SITE AMENITIES PERMIT WILL BE
 REQUIRED FOR SITE WALL, GATES, ETC...
  
 9) THE FIRST FLOOR OF ALL CONDOMINIMUM
 HAVING A RESTROOM OR BATHROOM,
 11-4.22.2(1) SHALL HAVE AT LEAST ONE
 RESTROOM OR
 BATHROOM WITH A CLEAR OPENING OF 29".
 SEE DIFINITION OF CLEAR OPENING,
 MINIMUM
 WIDTH OF 32".
  
 10) SHEET A2.1.1 & SHEET A2.1.2 BOTH
 BUILDINGS SHALL MEET THE MAXIMUM STAIR
 HEIGHT REQUIREMENT OF 7", MINIMUM
 HEIGHT
 OF 4" SEE 1007.3.1.
  
 11) STAIR CONSTRUCTION SEE A6.1.0.
 1007.1.1 INTERIOR STAIRWAYS SHALL BE
 CONSTRUCTED OF NONCOMBUSTIBLE MATERIALS
 THROUGHOUT IN THE FOLLOWING BUILDINGS:
 (3)ALL BUILDINGS 3 STORIES OR MORE IN
 HEIGHT.
  
 12) SHEET A2.1.1, A2.1.2 AND A7.3.0
 DOOR SCHEDULEPLANS DO NOT INDICATE
 THE OCCUPANCY SEPERATION REQUIRED FOR
 THE WALL NOR DOOR, SEE411.2.6 AND TABLE
  
 704.1.
  
 13) SHEET A2.3.1 & A2.3.2 PLANS DOESN'T
  
 SHOW WHERE THE ATTIC ACCESS? FL BLD
 CODE 2309.6 ATTIC ACCESS, PRO- VIDE
 ATTIC ACCESS 20"X36".
  
 14) VARIOUS SHEETS THROUGHOUT THE PLAN
 INDICATE CODE SECTIONS REGAURDING
 ROOFING,1518.9, 1518.2.1,1518.4,&
 1517.5.2. THESE CODE SECTIONS ARE FOR
 HIGH WIND ZONES, DADE & BROWARD
 COUNTIES
 AND UNENFORCEABLE.
  
 15) S-5 DETAIL # 1, SEE 2005 USP
 CATALOG
 FOR LISTING 2005 HIGH VALUE. SAME
 DETAIL
 SHEET S-6 DETAIL# 2.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD
 LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS
 OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE
 EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE
 LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS
 SPE
 CIFIED IN THE MATERIALS SECTIONS OF
 THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
  
 16)S-6 ROOF FRAMING PLAN NOTE # 2,
 CORRECT NOT IN HIGH VELOCITY ZONE.
  
 17) S-7 ROOF UPLIFT PRESSURES ARE LOW
 WHEN FIGURING A "C" ZONE WITH HEIGH
 FACTORS TABLE 1606.2D. REVISE
  
 18)EITHER ON ARCH. OR STRUCTURAL SHEETS
 (ELE) INDICATE POS & NEG WINDOW & DOOR
 PRESSURES. THE A7.40 ALLOWABLE WIND
 LOAD
 IS GIVEN BUT NOT THE ACTUAL WIND LOADS,
 NOR INDICATION IF LOCATION IS IN A END
 ZONE SEE 1606.2D FOR MULTIPLIERS FOR
 INDICATED "C" ZONE AND HEIGHT FACTORS.
  
 19) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)WINDOWS OPERATABLE & FIXED
 B) GLASS BLOCK
 C) MULLIONS
 D) EXTERIOR SOLID DOORS
 E) EXTERIOR GLASS/ SLIDING DOORS
 F) OVERHEAD GARAGE DOORS
 G) STORM SHUTTERS IF GLAZING NOT
 TESTED
 FOR LARGE MISSLE IMPACT
 H) SIDING
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
  
 21)1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 22)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 23) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026