Plan Review Notes
Plan Review Notes For Permit 04120934
Permit Number 04120934
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-30 00:00:00**************** UNSAT ****************
  
  
  
 1)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PLEASE SEE PLANS STILL NOTE ONLY
 RECEPTS.
  
 2)NOTE: PLEASE SEE MIN KW FOR WASHER.
 PER 220.16B A LOAD OF NOT LESS THAN 1500
 VOLT-AMPERES SHALL BE INCLUDED FOR EACH
 2-WIRE LAUNDRY BRANCH CIRCUIT INSTALLED
 AS REQUIRED BY 210.11(C)(2).
  
 3)NOTE: PLEASE SEE RECEPTS MISSING PER
 2' OF WALL SPACE PER 210.52
  
 4)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 5)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOTED FROM METER
 TO MAIN "B". PLEASE SEE 250.6,250.24 AN
  
 EQUIPMENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISC.
  
 6)NOTE: PLEASE SEE 250.66/ 310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR FOR
 300A SERVICE. MIN #2.
  
 7)NOTE: PLEASE SEE PERMIT APPLICATION
 IS
 BEING RETAINED FOR RECORD.
 ALL SUB CONTRACTORS SIGNED ON
 APPLICATION IS ACTUALLY PHOTOCOPIED OF
 ORIG SIGNATURES.ALL SUB CONTRACTORS
 SIGNED AND DATED ON APPLICATIONS MUST BE
 ORIGINAL SIGNATURE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]