| 2005-03-30 00:00:00 | PROVISO: | | | 1.TERMINATION FOR THE GREASE DUCT | | | SHALL BE MINIMUM OF 10 FT FROM PROPERTY | | | LINES, ADJACENT OR CONTIGUOUS BUILDINGS, | | | AND FRESH AIR INTAKES. | | | | | | 2.WELDS SHALL BE INSPECTED PRIOR TO | | | THE INSTALLATION OF THE 3M FIRE BLANKET | | | INDICATED ON PLAN SHEET 1.PROVIDE | | | INSTALLATION INSTRUCTIONS FOR THE FIRE | | | BLANKET ON THE JOBSITE AT THE TIME OF | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|