| Plan Review Notes For Permit 04120913 |
| Permit Number |
04120913 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-29 00:00:00 | PROVISO: | | | 1.ADDITIONAL PERMIT REQUIRED FOR THE | | | FIRE SUPPRESSION. PROVIDE PLANS SHOWING | | | COMPLIANCE WITH 2001 FBC(M)509 & NFPA | | | 96. | | | | | | 2.TERMINATION FOR THE GREASE DUCT | | | SHALL BE A MINIMUM OF 10 FT FROM | | | PROPERTY LINES, ADJACENT OR CONTIGUOUS | | | BUILDINGS, AND FRESH AIR INTAKES. | | | | | | 3.WELDS SHALL BE INSPECTED PRIOR TO | | | INSTALLATION OF THE 3M FIRE BLANKET | | | INDICATED ON PLAN SHEET 1.PROVIDE | | | INSTALLATION INSTRUCTIONS FOR THE FIRE | | | BLANKET ON THE JOBSITE AT THE TIME OF | | | INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|