2004-12-29 00:00:00PROVISO:
 1.ADDITIONAL PERMIT REQUIRED FOR THE
 FIRE SUPPRESSION. PROVIDE PLANS SHOWING
 COMPLIANCE WITH 2001 FBC(M)509 & NFPA
 96.
  
 2.TERMINATION FOR THE GREASE DUCT
 SHALL BE A MINIMUM OF 10 FT FROM
 PROPERTY LINES, ADJACENT OR CONTIGUOUS
 BUILDINGS, AND FRESH AIR INTAKES.
  
 3.WELDS SHALL BE INSPECTED PRIOR TO
 INSTALLATION OF THE 3M FIRE BLANKET
 INDICATED ON PLAN SHEET 1.PROVIDE
 INSTALLATION INSTRUCTIONS FOR THE FIRE
 BLANKET ON THE JOBSITE AT THE TIME OF
 INSPECTION.
  