| 2006-08-20 00:00:00 | ********* UNSAT ******** |
| | |
| | 1) NOTE: PLEASE CORRELATE PANELS, RISER |
| | AND PLANS. |
| | PLEASE SEE PANEL WHICH IS SHOWN ON RISER |
| | AS A 200 FEED-THRU PANEL, YET NO PANEL |
| | SCHEDULE ETC WAS SUBMITTED. |
| | PLEASE ALSO SEE THIS IS NOT SHOWN ON |
| | PLANS. |
| | THIS SHOUDL AHVE A MCB. |
| | 225.31, FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE CORRELATE SIZES OF |
| | PANELS ON PANEL SCHEDULES AND WHAT IS |
| | BEING SHOWN ON RISER. |
| | |
| | 3) NOTE: PLEASE CORRELATE FEEDERS ON |
| | RISER AND PANEL SCHEDULES. PLEASE SEE |
| | 3/0, AND #1'S ETC FOR 100A BRKR FEED TO |
| | THE SUB PANEL. |
| | |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULE |
| | CIRCUTING DOES NOT SEEM TO START UNTIL |
| | ABOUT 1/3 THE WAY DOWN THE PANEL. |
| | PLEASE VERIFY THIS AS THIS IS NOT THE |
| | WAY IT IS ON THE JOBSITE. |
| | |
| | |
| | ** PLEASE KNOW, MANY ITEMS ON THE |
| | JOBSITE DOES NOT MATCH WITH PLANS. |
| | PLEASE KNOW, A PLAN REVIEW WAS DONE WITH |
| | THE ELECTRICAL INPECTOR AND CONTRACTOR |
| | ON THE PHONE AND MANY ITEMS SHOWN ON |
| | THESE PLANS DO NOT MATCH WITH WHAT IS |
| | INSTALLED IN FIELD. PLEASE GET WITH THE |
| | CONTRACTOR AND VERIFY ALL. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |