| Date |
Text |
| 2006-08-09 00:00:00 | **** UNSAT ****** |
| | |
| | |
| | |
| | 1) NOTE: THIS SEE THIS IS NOT A |
| | RE-STAMP. |
| | SUBMIT TWO COMPLETE COPIES FOR REVISIONS |
| | AND PAY REVISION FEES. |
| | PLEASE ALSO SEE NOTES FROM PREVIUOUS |
| | REVIEW WHICH FAILED. |
| | NOTES BELOW ARE ATTACHED. |
| | |
| | |
| | ******** UNSAT ******** FROM 7/27/06 |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT THE PREVIOUS |
| | PLANS WERE REDLINED AS THE GENERATOR |
| | SHOWN ON PLANS WAS NOT PART OF THE |
| | PERMIT FOR THE HOUSE AND NO PERMIT TO |
| | DATE HAS BEEN APPLIED FOR THE |
| | RESIDENTIAL GEN. PLEASE REMOVE FROM |
| | PLANS. |
| | (SHOWS 5KW UNIT, IS THIS NOT A PRTABLE |
| | UNIT? ) |
| | |
| | 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | WITH ALL CIRCUITS SPECIFIC TO AREAS AND |
| | ROOMS IN WHICH THEY FEED. PLEASE SEE |
| | 408.4. IE, MASTER BEDRN LTS, LIVING RM |
| | RECEPTS, HALL LTS, ETC. |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHOWS A |
| | "TANKLESS" WATER HEATER FOR THE MAIN |
| | HOUSE. PLEASE SEE HOWEVER THE KW RATING |
| | SEEMS TO BE FOR A STANDARD WH UNIT.?? |
| | PLEASE SEE TL WH'S FOR A HOUSE THIS SIZE |
| | IS TPICALLY MUCH LARGER. PLEASE VERIFY |
| | AND ADJUST LOAD CALCS. |
| | 220 |
| | |
| | 4) NOTE: PLEASE SEE THERE ARE A FEW |
| | LOCATIONS ON PLANS WHERE LV UC PUCK LT |
| | ARE NOTED , HOWEVER HOW MANY AND |
| | LOCATIONS ARE NOT SHOWN. PLEASE CLARIFY. |
| | |
| | 5) NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | FOR PANELS A AND B. 215.5,220.31. |
| | |
| | 6) NOTE: PLEASE CORRELATE RISER AND |
| | PANELS. PLEASE SEE RISER SHOWS 20CIRCUIT |
| | PANELS FOR "C" AND "B", HOWEVER THESE |
| | ARE SHOWN AS 40 CIRCUIT PANELS ON |
| | SCHEDULES. |
| | |
| | 7) NOTE: PLEASE KNOW IF THESE PLANS ARE |
| | FOR FINAL WHICH THEY APPEAR TO BE. |
| | PLEASE SEE TAHT ANY "OPT" LISTED ON |
| | PLANS EITHER ARE IN OR ARE REMOVED AS |
| | OPTIONAL. |
| | PLANS SHALL CONTAIN AN ACCUREATE RECORD |
| | OF THE SCOPE OF WORK PERFORMED ON JOB |
| | SITE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |