| 2005-09-15 00:00:00 | BUILDING REVISION |
| | DENIED |
| | |
| | |
| | 1) BOTH SETS OF REVISED DRAWINGS ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT AND THE ENGINEER THAT SIGNED |
| | AND SEALED THE ORIGINAL PLANS. FS 471 |
| | AND 481. |
| | |
| | 2) REMOVE THE 4:12 ROOF PITCH INDICATION |
| | FROM THE REAR GARAGE ELEVATION ON A5. |
| | |
| | 3) THE GARAGE FLOOR FRAMING PLAN ON S-7 |
| | INDICATES A GARAGE WALL SECTION 1 ON S5. |
| | THIS SECTION SPECIFIES A PITCHED ROOF. |
| | PLEASE CORRECT. |
| | |
| | 4) SPECIFY THE SECOND FLOOR CEILING |
| | INSULATION AS REQUIRED BY FBC CHAPTER |
| | 13. MUST CORRESPOND TO ENERGY CALC. |
| | FORMS. |
| | |
| | 5) SPECIFY ATTIC VENTILATION PER FBC |
| | 2309.7. |
| | |
| | |
| | |
| | 6) ATTIC ACCESS IS NO LONGER REQUIRED |
| | PER FBC 2309.6. REVISE SHEET A2 OR SHOW |
| | THE 22" WIDE SPACE BETWEEN TRUSSES THAT |
| | ARE 16"OC ON THE ROOF FRAMING PLAN ON |
| | S7. |
| | |
| | 7) THE PARAPET DETAIL ON S8 SPECIFIES A |
| | SIMPSON RT16 ATTACHED TO A CONCRETE BEAM |
| | WITH TAPCONS. SIMPSON DOES NOT LIST THIS |
| | CONNECTOR IN THEIR 2005 CATALOG. USP |
| | DOES HAVE A RT16 CONNECTOR, HOWEVER IT |
| | IS NOT SPECIFIED FOR ATTACHMENT TO |
| | CONCRETE BEAMS. IF THERE IS A TECHNICAL |
| | BULLETIN THAT SPECIFES THIS APPLICATION, |
| | PLEASE SUBMIT TWO COPIES OR REVISE PLANS |
| | TO SPECIFY A CONNECTOR DESIGNED AND |
| | TESTED FOR THIS APPLICATION. |
| | |
| | 8) SPECIFY THE TYPE AND NUMBER OF |
| | FASTENERS FOR THE SIMPSON U212 HANGER |
| | SPECIFIED ON S8. SUBMIT THE FLORIDA |
| | PRODUCT APPROVAL FOR THIS CONNECTOR. |
| | |
| | 9) SPECIFY THE WELD TYPE THAT WILL BE |
| | USED TO ATTACH THE THREADED RODS TO THE |
| | BRACKET IN DETAIL 4A ON S8. WHY ARE |
| | THREADED RODS BEING USED RATHER THAN |
| | NELSON STUDS. |
| | |
| | 10) THE ROOF DOWN SPOUTS SHALL DISCHARGE |
| | AT LEAST 1 FOOT AWAY FROM THE STRUCTURE |
| | SIDEWALL PER FBC 1503.4.4. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |