| Date |
Text |
| 2005-03-01 00:00:00 | ********** UNSAT ************** |
| | |
| | PLEASE SEE DUE TO ADDRESS CHANGE AND |
| | PLANS SUBMITTED FOR THIS PERMIT # |
| | ORIGINALLY, PLEASE SEE COMMENTS BELOW |
| | WHICH STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE MAIN HOUSE PANEL IS |
| | SHOWN AT DETACHED BLDG. |
| | PLEASE SEE 225.31,32,36,250.32 |
| | PLEASE SEE RISER NOW INDICATES A 300A |
| | DISC FEEDING A 200A RATED PANEL AND A |
| | 150A RATED PANEL. |
| | PLEASE VERIFY OCP FOR EACH OF THESE |
| | PANELS. |
| | 300A OCP MAY NOT FEED THESE. |
| | PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDGS. |
| | MEANS SHALL BE PROVIDED FOR |
| | DISCONNECTING ALL UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE BUILDING |
| | OR STRUCTURE. |
| | THE DISCONNECTING MEANS SHALL BE |
| | INSTALLED EITHER INSIDE OR OUTSIDE OF |
| | THE BUILDING OR STRUCTURE SERVED OR |
| | WHERE THE CONDUCTORS PASS THROUGH THE |
| | BUILDING OR STRUCTURE. THE DISCONNECTING |
| | MEANS SHALL BE AT A READILY ACCESSIBLE |
| | LOCATION NEAREST THE POINT OF ENTRANCE |
| | OF THE CONDUCTORS. FOR THE PURPOSES OF |
| | THIS SECTION, THE REQUIREMENTS IN 230.6 |
| | SHALL BE PERMITTED TO BE UTILIZED. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| | FOR MISSING SD'S REQUIRED AT SECOND FLR |
| | GUEST SUITE/RM AND ALSO AT FLR AREA |
| | LEADING TO FLR ABOVE. |
| | |
| | 3)NOTE: PLEASE SEE PLANS CALL FOR SECOND |
| | FLR AREA TO BE A "GAME ROOM" HOWEVER, |
| | PANEL SCHEDULES INDICATE GUEST SUITE. |
| | PLEASE SEE POSSIBLE ZONING COMMENTS FOR |
| | THIS. |
| | |
| | 4)NOTE: PLEASE SEE SMALL APPLIANCE |
| | CIRCUIT SHOWN AS 15A/ #12 AWG. |
| | PLEASE SEE 210.11C1,220.16 FOR MIN 20A |
| | #12. |
| | |
| | 5)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS AFTER THE FIRST |
| | MEANS OF DISCONNECT. 250.24. PLEASE SIZE |
| | PER 250.122 |
| | |
| | 6)NOTE: PLEASE SEE ALL CIRCUITING ON |
| | PANEL SCHEDULES ARE TO BE REVISED. |
| | PLEASE SEE PANEL "B" WHICH SHOULD BE |
| | DETACHED GARAGE/GM RM/GUEST SUITE IS |
| | SHOWING 17 LIGHTING CIRCUITS, WHICH MOST |
| | SHOULD BE ON PANEL FOR MAIN HOUSE. |
| | |
| | |
| | PLEASE SEE DUE TO PLANS SUBMITTED FOR |
| | DIFFERENT HOUSES ON DIFFERENT LOTS. SOME |
| | OF THESE COMMENTS MAY ALSO BE ON PERMIT |
| | #04120901 |
| | |
| | |
| | PLEASE CALL TO GO OVER ANY QUESTIONS FOR |
| | ELECTRICAL COMMENTS AND POSSIBLE |
| | CORRECTION OPTIONS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |