| Date |
Text |
| 2005-01-07 00:00:00 | DENIED |
| | 1)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | |
| | 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD |
| | ZONE AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. THE MINIMUM ELEVATION IS |
| | 7.5',WHICH INCLUDES AN ADDITIONAL 6" |
| | ABOVE BASE FLOOD ELEVATION PER CITY OF |
| | WPB ORDINANCE. |
| | |
| | 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 4) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORM. THE SQUARE |
| | FOOTAGE OF CONDITIONED SPACE ON THE FORM |
| | DOES NOT AGREE WITH THE AMOUNT SPECIFIED |
| | ON THE PLANS. SECTION A ON S4 AND THE |
| | ENERGY CALC. INFO ON A1 SPECIFIES FOAM |
| | BOARD INSULATION AND THE ENERGY CALCS. |
| | LIST R-4.1.PLEASE CORRECT. |
| | |
| | 5) SPECIFY ON THE PLANS THAT THE |
| | INTERMEDIATE RAILS OF THE GUARDRAILS AT |
| | THE STAIRS AND BALCONIES ARE REQUIRED TO |
| | REJECT A 4" SPHERE AND THE BOTTOM RAIL |
| | SHALL REJECT A 2" SPHERE. SEE FBC 1015.3 |
| | |
| | |
| | 6) SPECIFY FIREBLOCKING AT THE ENCLOSED |
| | SPACES BETWEEN STAIR STRINGERS AT THE |
| | TOP AND BOTTOM OF RUNS. SEE FBC |
| | 2305.1.4 |
| | |
| | 7) THE STAIR CALCS ON A1 AND A2 CONTAIN |
| | ERRORS. PLEASE CORRECT. |
| | |
| | 8) SHOP DRAWINGS WILL BE REQUIRED FOR |
| | THE ALUMINUM GUARDRAILS AT THE STAIRS |
| | AND BALCONIES. |
| | |
| | 9) THE CITY OF WPB AMENDMENTS TO FBC |
| | TABLE 2306.1 REQUIRES ROOF SHEATHING TO |
| | BE NAILED AT 4"OC AT EDGES AND 6"OC |
| | INTERMEDIATE IN ZONE THREE WITH 8D RING |
| | SHANK NAILS WHEN MEAN ROOF HEIGHT IS |
| | 25'-35'. THE OUTSIDE CORNERS OF HIP |
| | ROOFS ARE ZONE 3. |
| | |
| | 10) FBC 1006.2.4 REQUIRES THE WALLS |
| | ADJACENT TO THE EXTERIOR EXITWAY STAIRS |
| | AND COVERED PORCH TO HAVE A ONE HOUR |
| | RATING WITH OPENING PROTECTIVES. |
| | |
| | 11) SUBMIT MANUFACTURER'S SPECS. AND |
| | LISTING INFORMATION FOR THE BUILT-IN |
| | GAS |
| | BBQ. |
| | |
| | 12) THE PLANS SHOW VENTED PREFAB |
| | FIREPLACES WITH FLUES TO THE ROOF. THE |
| | PRODUCT APPROVAL SUBMITTED IS FOR |
| | VENTLESS FIREPLACES. PLEASE CLARIFY. |
| | |
| | 13) FBC 1707.4.4.2 REQUIRES WINDOW AND |
| | DOOR FRAMES TO BE FASTENED THROUGH 1X |
| | BUCKS AND INTO THE STRUCTURAL SUBSTRATE. |
| | PLEASE CORRECT BUCK NOTE ON A1. |
| | |
| | 14) PROVIDE A FOOTING DETAIL AT THE |
| | GARAGE DOOR OPENING. |
| | |
| | 15) THE SPECIFIED THICKNESS OF THE |
| | FOOTER IN DETAIL G ON S1 IS NOT |
| | CORRECT. |
| | |
| | 16) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 17) SUBMIT (2) COMPLETE, CLEAN AND |
| | LEGIBLE COPIES OF PRODUCT APPROVALS. |
| | THE FOLLOWING SUBMITTALS HAVE SOME PAGES |
| | THAT ARE ILLEGIBLE: |
| | - PGT PW 701 |
| | - WINDSOR GARAGE DOOR |
| | - MULE-HIDE ROOFING |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |