| Notes |
| Date |
Text |
| 2006-01-20 00:00:00 | ********** UNSAT ************* | | | | | | 1)NOTE: PLEASE CORRELATE RISER AND | | | PLANS. PLEASE SEE RISER HAS NOW BEEN | | | REVISED AND SHOWS AN ADDITIONAL RISER?? | | | PLEASE SEE RISER SHOWS CU'S BEING FED | | | FROM THESE OUTDOOR PANELS, HOWEVER NO | | | OCP, AWG, OR LOADS ARE SHOWN FOR THESE | | | CU'S.? | | | PLEASE SEE PLANS INDICATE 3-220V DISC'S | | | NEXT TO METER, PLEASE SEE IT WAS ASSUMED | | | THESE WERE THE DISC'S FOR POOL PUMP, AND | | | CU'S HOWEVER THIS IS NOT CLEAR. PLEASE | | | CORRELATE PLANS WITH SERVICE EQUIPMENT | | | AND RISER DIAGRAM. | | | 215.5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|