| Plan Review Notes For Permit 04120901 |
| Permit Number |
04120901 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-12-29 00:00:00 | REVISIONS DENIED | | | | | | 1) SUBMIT REVISED ENERGY CALCULATIONS | | | FOR R-20 INSULATION. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS | | | AND INSTALLATION INSTRUCTIONS FOR THE | | | ICYNENE INSULATION. | | | | | | 3) ICYENE INSULATION IS TYPICALLY USED | | | FOR UNVENTED ATTICS AND IS INSTALLED ON | | | THE TOP CORD OF THE TRUSSES. THE | | | SECTIONS ON S-4 SPECIFY INSTALLATION ON | | | THE BOTTOM CORD. IF APPLIED TO THE | | | BOTTOM CORD THE ATTIC VENTILATION MUST | | | BE MAINTAINED AND RECESSED LIGHTING WILL | | | BE AFFECTED. PROVIDE MANUFACTURER'S | | | INFORMATION WHICH ADDRESSES THESE ITEMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|