Plan Review Notes
Plan Review Notes For Permit 04120901
Permit Number 04120901
Review Stop E
Sequence Number 4
Notes
Date Text
2005-11-10 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE VERIFY DRYER(S) AND
 WASHER(S).
 PLEASE SEE PLANS INDICATE TWO DRYERS AND
 TWO WASHER RECEPTS SHOWN AT THIS SAME
 LOCATION, HOWEVER PANEL SCHEDULE AND
 LOAD CALCULATIONS ONLY INDICATE ONE
 WASHER?
 PLEASE ALSO CALRIFY IF THESE UNITS A
 STACKABLE UNITS AND PERHAPS THE 120V
 RECEPTS ARE ONLY PLACED FOR POSSIBLE
 FUTURE INDIVIDUAL UNITS.??
  
 2)NOTE: PLEASE VERIFY THE LOAD ON GDO'S
 AS 1/4 HP OR MORE REQUIRES DEDICATED
 CIRCUITS AND MAY NOT SHARE OTHER MOTOR
 LOADS.430.53, 430.148
  
 3)NOTE: PLEASE SEE REDLINED PLANS FOR
 POSSIBLE MISSING RECEPTS PER 210.52, 2'
 OF WALL SPACE.
 PLEASE SEE THAT RAIL AREA IN LOFT RM, IS
 CONSIDERED WALL SPACE AND WILL BE
 REQUIRED TO HAVE A RECEPT(FLOOR).
  
  
 4)NOTE: PLEASE SEE POSSIBLE
 KITCHEN/BUTLER COUNTERSPACE FOR MISSING
 GFI RECEPT(S) PER 210.52C1
 THESE LOCATIONS ARE REDLINED TO BE
 VERIFIED.
  
 5)NOTE: PLEASE SEE 210.8A2 WHICH
 REQUIRES ALL OUTDOOR RECEPT READILY
 ACCESSIBLE (6 1/2' ) OR LESS TO BE
 GFI/GFI PROTECTED.
 REDLINED.
  
 6)NOTE: PLEASE SEE PLANS INDICATE
 2-DISPOSAL'S, YET, PANEL SCHEDULES AND
 LOAD CALCULATIONS, ONLY INDICATE ONE?
 PLEASE CORRELATE AND ADJUST.
 215.5
  
 7)NOTE: PLEASE SEE LOAD CALCS INDICATE
 THREE SMALL APPLIANCE CIRCUITS, YET
 PANEL SCHEDULES ONLY SHOW TWO.
 PLEASE CORRELATE AND ADJUST AS NESS.
 215.5
  
 8)NOTE: PLEASE CORRLELATE THE NUMBER OF
 RECESSED LTS ON LOAD CALCULATIONS, WITH
 THE NUMBER OF FIXTURES SHOWN ON PLANS.
 PLEASE ADJUST LOAD CALCS AS NEEDED.
 215.5, 220.4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  