| Plan Review Notes For Permit 04120901 |
| Permit Number |
04120901 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-26 00:00:00 | DENIED; | | | 1.LAUNDRY TUB REQUIRED TO DISCHARGE | | | ABOVE WASHER. | | | 2.CLOTHS WASHER WASTE ARM AND TRAP TO BE | | | TWO INCH. | | | 3.RISER DIAGRAM DOES NOT MATCH FLOOR | | | PLAN.(LAUNDRY ROOM ON SAME WALL AS | | | KITCHEN, LAUNDRY ROOM IS NEAR DINING | | | ROOM KITCHEN IS NEAR GARAGE. 3' RISERS | | | FOR 2ND FLOOR ARE OUTSIDE HOUSE) | | | 4.3" RISERS FOR 2ND FLOOR REQUIRE A 6" | | | WALL PLEASE SHOW ON DRAWING. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|