Plan Review Notes
Plan Review Notes For Permit 04120901
Permit Number 04120901
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-24 00:00:00******* UNSAT *******
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 ZONING COMMENTS.
 PLEASE CORRECT AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER HAS NOW
 INCREASED ORIG 100A PANEL TO 150A'S.
 PLEASE SEE CONDUCTORS WERE NOT INCREASED
 FOR 150A'S, PLEASE SEE 310.15B6 MIN,
 310.16.
 PLEASE CORRELATE PANEL , PLEASE SEE
 PANEL DETAILS LOCATED AT BOTTOM OF PANEL
 BOTH INDICATE 100A MAIN AND 150A.
 215.5
  
 2)NOTE: PLEASE SEE ELECTRICAL PLANS NOW
 INDICATE AN OPENING INTO SECOND FLR
 MEDIA RM, HOWEVER NO MEANS FOR SWITCHING
 OF EGRESS LIGHTINGIS SHOWN. PLANS
 REDLINED ON ONE SET. (3-WAY SWITCH)?.
  
 3)NOTE: PLEASE SEE 310.15B6,250.66, DUE
 TO INCREASE IN SIZE OF SERVICE, PLEASE
 SEE MIN GROUNDING ELECTRODE CONDUCTOR IS
 NOW 1/0. PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE EACH SD HAS A RECEPT
 SHOWN NEXT TO IT? THIS SEEMS TO BE
 EITHER AT CEILING OR AT FLR? PLEASE
 VERIFY IF THIS RECEPT IS GOING BE
 INSTALLED AT EACH SD LOCATION?
 THIS IS ONLY A NOTE: PLANS ARE COMING
 BACK AND IF ANY CHANGES NEEDED TO MADE,
 THIS WOULD SAVE FROM HAVING TO REVISE
 PLANS AGAIN BEFORE ROUGH.
  
 PLEASE SEE ONE SET OF PLANS HAVE AREAS
 REDLINED AT LOCATIONS FOR NOTES.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-02-23 00:00:00FROM ZONIING TO ELECTRIC REVIEW ON
 2/19/05