| 2005-02-24 00:00:00 | ******* UNSAT ******* |
| | |
| | PLEASE SEE PLANS ARE COMING BACK FOR |
| | ZONING COMMENTS. |
| | PLEASE CORRECT AT THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE RISER HAS NOW |
| | INCREASED ORIG 100A PANEL TO 150A'S. |
| | PLEASE SEE CONDUCTORS WERE NOT INCREASED |
| | FOR 150A'S, PLEASE SEE 310.15B6 MIN, |
| | 310.16. |
| | PLEASE CORRELATE PANEL , PLEASE SEE |
| | PANEL DETAILS LOCATED AT BOTTOM OF PANEL |
| | BOTH INDICATE 100A MAIN AND 150A. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE ELECTRICAL PLANS NOW |
| | INDICATE AN OPENING INTO SECOND FLR |
| | MEDIA RM, HOWEVER NO MEANS FOR SWITCHING |
| | OF EGRESS LIGHTINGIS SHOWN. PLANS |
| | REDLINED ON ONE SET. (3-WAY SWITCH)?. |
| | |
| | 3)NOTE: PLEASE SEE 310.15B6,250.66, DUE |
| | TO INCREASE IN SIZE OF SERVICE, PLEASE |
| | SEE MIN GROUNDING ELECTRODE CONDUCTOR IS |
| | NOW 1/0. PLEASE ADJUST. |
| | |
| | 4)NOTE: PLEASE SEE EACH SD HAS A RECEPT |
| | SHOWN NEXT TO IT? THIS SEEMS TO BE |
| | EITHER AT CEILING OR AT FLR? PLEASE |
| | VERIFY IF THIS RECEPT IS GOING BE |
| | INSTALLED AT EACH SD LOCATION? |
| | THIS IS ONLY A NOTE: PLANS ARE COMING |
| | BACK AND IF ANY CHANGES NEEDED TO MADE, |
| | THIS WOULD SAVE FROM HAVING TO REVISE |
| | PLANS AGAIN BEFORE ROUGH. |
| | |
| | PLEASE SEE ONE SET OF PLANS HAVE AREAS |
| | REDLINED AT LOCATIONS FOR NOTES. |
| | |
| | PLEASE REMOVE OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |