| Date |
Text |
| 2004-12-23 00:00:00 | ********** UNSAT **************** |
| | |
| | |
| | 1) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 2)NOTE: PLEASE SEE 210.52D FOR LOCATION |
| | OF GFI RECEPT SPACING TO WITHIN 3' OF |
| | SINK EDGE. |
| | |
| | 3)NOTE: PLEASE SEE 210.63, 210.70 FOR |
| | GFI RECETP AND LT REQUIRED FOR AHU |
| | OUTSIDE MECH RM. |
| | |
| | 4)NOTE: PLEASE VERIFY KW LOAD SHOWN FOR |
| | WATER HEATER AND OVENS. WH IS SHOWN AS |
| | 80 GAL YET ONLY SHOWS 5KW HEAT? |
| | PLEASE ALSO SEE DOUBLE OVENS ARE SHOWN |
| | WITH 50A OCP YET TWO OVENS ARE ONLY |
| | SHOWN WITH 6KW LOAD?? |
| | PLEASE VERIFY THE ABOVE AND ADJUST AS |
| | NEEDED. |
| | |
| | 5)NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS |
| | ON PLANS. |
| | |
| | 6)NOTE: PLEASE INDICATE GFI FOR |
| | JACUZZI/SPA TUB. PER 680 |
| | |
| | |
| | 7 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY |
| | NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 8)NOTE: PLEASE SEE ZONING COMMENTS FOR |
| | APT AREA SHOWN ABOVE GARAGE. |
| | THIS WILL AFFECT ELECTRICAL PLANS. |
| | |
| | 9)NOTE: PLEASE SEE MAIN HOUSE PANEL IS |
| | SHOWN AT DETACHED BLDG. |
| | PLEASE SEE 225.31,32,36 |
| | 250.31 |
| | MEANS SHALL BE PROVIDED FOR |
| | DISCONNECTING ALL UNGROUNDED CONDUCTORS |
| | THAT SUPPLY OR PASS THROUGH THE BUILDING |
| | OR STRUCTURE. |
| | THE DISCONNECTING MEANS SHALL BE |
| | INSTALLED EITHER INSIDE OR OUTSIDE OF |
| | THE BUILDING OR STRUCTURE SERVED OR |
| | WHERE THE CONDUCTORS PASS THROUGH THE |
| | BUILDING OR STRUCTURE. THE DISCONNECTING |
| | MEANS SHALL BE AT A READILY ACCESSIBLE |
| | LOCATION NEAREST THE POINT OF ENTRANCE |
| | OF THE CONDUCTORS. FOR THE PURPOSES OF |
| | THIS SECTION, THE REQUIREMENTS IN 230.6 |
| | SHALL BE PERMITTED TO BE UTILIZED. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| | REFERENCE ONLY. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |