| 2005-01-05 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) THE STRUCTURES ARE LOCATED IN AN "A5" |
| | FLOOD ZONE. AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. THE MINIMUM ELEVATION |
| | IS 7.5', WHICH INCLUDES AN ADDITIONAL |
| | 6" PER CITY OF WEST PALM BEACH |
| | ORDINANCE. |
| | |
| | 4) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 5) SPECIFY THE INSULATION R-VALUE OF THE |
| | FLOOR OF THE GUEST HOUSE. SHEET S5 |
| | SPECIFIES R-19. |
| | |
| | 6) SPECIFY ON THE PLANS THAT THE |
| | INTERMEDIATE RAILS OF GUARDRAILS AT |
| | STAIRS AND BALCONIES ARE REQUIRED TO |
| | REJECT A 4" SPHERE AND THE BOTTOM RAIL |
| | SHALL REJECT A 2" SPHERE. SEE FBC |
| | 1015.3 |
| | |
| | 7) SPECIFY FIREBLOCKING AT THE ENCLOSED |
| | SPACES BETWEEN STAIR STRINGERS AT THE |
| | TOP AND BOTTOM OF RUNS. SEE FBC |
| | 2305.1.4 |
| | |
| | 8) ON S1 THE FTG.DETAILS D & I THE PAD |
| | FOOTER DEPTH IS INCORRECT. |
| | |
| | 9) THE GARAGE WALL SECTION 1 ON S5 DOES |
| | NOT MATCH THE FTG. DETAIL B ON S1. |
| | |
| | 10) ON S1 FTG DETAIL B IS INCORRECTLY |
| | SPECIFIED AT THE GARAGE DOOR OPENING. |
| | |
| | 11) THE CITY OF WEST PALM BEACH |
| | AMENDMENTS TO FBC TABLE 2306.1 REQUIRES |
| | THE ROOF SHEATHING TO BE NAILED AT 4"OC |
| | AT EDGES AND 6" OC INTERMEDIATE IN ZONE |
| | 3 WHICH INCLUDES THE OUTSIDE CORNERS OF |
| | HIP ROOFS. |
| | |
| | 12) SHOP DRAWINGS WILL BE REQUIRED TO BE |
| | SUBMITTED FOR EXTERIOR IRON GUARDRAILS |
| | AT STAIRS AND BALCONY FOR APPROVAL PRIOR |
| | TO THEIR INSTALLATION. |
| | |
| | 13) THE EXTERIOR EXITWAY STAIRS AND |
| | PORCHES,ETC. ARE REQUIRED TO BE LOCATED |
| | A MINIMUM OF 10' FROM ADJACENT PROPERTY |
| | LINES. BALCONIES, PORCHES , ETC. SHALL |
| | BE NOT LESS THAN 4.5' WIDE. SEE FBC |
| | 1006.2.2 |
| | |
| | 14) FBC 1006.2.4 REQUIRES WINDOWS WITHIN |
| | 10' OF EXTERIOR EXIT STAIRS TO HAVE |
| | OPENING PROTECTIVES. SEE FBC 1006.2.4 |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT TWO |
| | (2) LEGIBLE COPIES FOR EACH ITEM. |
| | |
| | 16) SUBMIT (2) TWO CLEAN LEGIBLE COPIES |
| | OF ALL PRODUCT APPROVALS. - SUBMIT |
| | PRODUCT APPROVALS FOR THE FOLLOWING: |
| | - ARCHED TOP DOOR SPECIFIED ON THE PLANS |
| | FOR THE CABANA BATH. |
| | - THERMA-TRU FIBERGLASS DOOR |
| | - CASEMENT WINDOWS |
| | - ROOF COVERING FOR FLAT ROOFS |
| | - ROOFING MATERIAL AT SUN DECKS |
| | - OVERHEAD GARAGE DOOR |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |