| Plan Review Notes For Permit 04120830 |
| Permit Number |
04120830 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-10-01 00:00:00 | DENIED; | | | 1.WATER RISER DIAGRAMS; | | | , | | | SHOCK ARRESTORS REQ. ON KITCHEN AND | | | WASHING MACHINE SEC.604.9 (ALL 4 RD'S) | | | THERMAL EXPANSION TANKES, PER. | | | MANUFACTUES INSTALLATION INSTRUCTIONS | | | TANK TO BE ON COLD WATER. ALL (4RD'S) | | | SHUTOFF VALVES REQUIRED FOR EACH UNIT | | | SHOW ON RISER DIAGRAM | | | WATER RISER DIAGRAM 2ND FLOOR REAR W/M | | | NOT SHOWN. ONE PLAN MARKED IN RED | | | 2. SANITARY RISER DIAGRAMS; | | | W/C FIRST FL NOT IN BATHROOM GROUP. | | | 2ND FL. ONLY A SHOWER ON FL PLAN NO | | | TUB. | | | 1ST AND 2ND FL MISSING W/M'S | | | BACK BUILDING, 4 BATHROOMS SHOWN ONLY | | | TWO ON FLOOR PLAN. | | | W/M'S NOT SHOWN ON RISER DIAGRAM. | | | 3.WATER HEATERS ON PLANS 5 ARE SHOWN | | | PLEASE DELETE ONE. | | | 4. SEE NOTE 15 BUILDING PLAN REVIEW. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | | | | | | | |
|