| Plan Review Notes For Permit 04120830 |
| Permit Number |
04120830 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-11 00:00:00 | ************ PROVISO/ REVISION ******** | | | | | | | | | 1)NOTE: PLEASE SEE RISER DIAGRAM SHOWS | | | ONE 125A DISCONNECT AT MAIN SERVICE | | | LOACTION FEEDING ONLY ONE DISCONNECT AT | | | DETACHED BLDG. PLEASE SEE THE ONE | | | DISCONNECT FEED BOTH PANELS. | | | PLEASE SEE OTHER DISC AT MAIN SERVICE | | | DOES NOT FEED ANYTHING.??? | | | PLEASE CORRELATE AND LABEL EACH. | | | UNIT, A | | | | | | 2)NOTE: PLEASE SEE SERVICE ENT | | | CONDUCTORS SHALL BE A MIN OF 400 MCM, | | | 310.15B6, 240.4, 90.8, 90.4. | | | | | | | | | 3)NOTE: PLEASE SEE SOME RECEPTS MISSING | | | PER 210.52 | | | | | | | | | PLEASE SUBMIT THE ABOVE REVISED PLANS | | | BEFORE ANY INSPECTION IS CALLED IN SO | | | THE PLANS CAN BE REVIEWED, STAMPED AND | | | BACK TO CONTRACTOR FOR THE FIRST | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|