| Date |
Text |
| 2004-12-23 00:00:00 | **************** UNSAT ************* |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO |
| | BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| | GROUNDING ELECTRODE CONDUCTOR. |
| | |
| | 3)NOTE: PLEASE CLARIFY WHICH LOCATION |
| | SERVICE IS GOING TO BE? |
| | SHOWN ON REAR BLDG AND MAIN FRONT |
| | BLDG?? |
| | PLEASE SEE 230.72 FOR REQUIRED GROUPING |
| | OF MAINS. |
| | |
| | 4)NOTE: PLEASE SEE 225.31,32.36 FOR |
| | MEANS OF DISC AT DETACHED BLDGS. PLEASE |
| | ALSO SEE 250.32 FOR GROUNDING. |
| | |
| | |
| | |
| | 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 6)NOTE: PLEASE SHOW ALL AC/ EQUIPMENT |
| | ON |
| | PLANS ALONG WITH REQUIRED DISC'S, |
| | RECEPTS PER . 215.5,440.11,210.63 |
| | |
| | 7)NOTE: PLEASE SEE 310.16 FOR SIZING OF |
| | SEC'S PER 240.4B |
| | |
| | 8)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDIG FROM MAINS TO PANELS. |
| | LOCAL AMENDMENTS: |
| | |
| | 9)NOTE:PLEASE SEE 2002 NEC 210.12 FOR |
| | ARC FAULT PROTECTION. |
| | |
| | 10)NOTE: PLEASE SEE FAC 61G15-23.002 |
| | FOR |
| | MISSING REQUIRED INFORMATION ON TITLE |
| | BLOCK. |
| | REQUIRED UNDER FS 471.023 |
| | |
| | 11)NOTE: PLEASE SEE #12 AWG ON 30A OCP |
| | FOR WATER HEATER. |
| | PLEASE SEE 310.16/240.4B |
| | |
| | PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| | OTHER REVIEWERS WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |