| 2004-12-28 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | |
| | 1.)SEE PROPERTY APPRISER VALUATION |
| | ATTACHED.THIS IS AN OVER 50% |
| | IMPROVEMENT AND MUST COMPLY WITH |
| | FBC3401.7.2.6.THIS SECTION AFFECTS |
| | OTHER COMMENTS ON THIS LIST. |
| | |
| | 2.)PROVIDE A COPY OF THE SURVEY FOR |
| | THIS PROPERTY. |
| | |
| | 3.)THIS APPEARS TO BE TWO UNITS; ONE |
| | UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS |
| | TO BE IMPACT GLASS, CITY OF WEST PALM |
| | BEACH IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION, |
| | ITEM #13, SEE ATTACHED.SUBMIT A |
| | HURRICANE INSTALLATION PLAN INCLUDING |
| | WHERE THE SHUTTERS WILL BE STORED FOR |
| | SHUTTERS USED ON THE FIRST FLOOR. |
| | |
| | 4.)THE BALCONY (MEANS OF EGRESS FOR |
| | 2ND FLOOR UNIT) IS TO COMPLY WITH |
| | FBC1014.1.SHOW FIRE RESISTANCE (UL |
| | ASSEMBLY OR CALCULATED FBC CHAPTER 7), |
| | PROVIDE DOOR FIRE RATING INFORMATION. |
| | |
| | 5.)THE EXTERIOR STAIR IS TO COMPLY |
| | WITH FBC1006.2.4.SHOW FIRE RESISTANCE |
| | OF THE WALL.OPENINGS WITHIN 10' ARE |
| | TO |
| | BE 3/4 HR.INDICATE ON THE PLAN. |
| | |
| | 6.)PROVIDE TENANT SEPARATION FIRE |
| | RESISTANCE INFORMATION FBC704.3. |
| | |
| | 7.)A 24 WINDOW DOES NOT COMPLY WITH |
| | EMERGENCY EGRESS REQUIREMENTS |
| | FBC1005.4. |
| | |
| | 8.)THIS PROPERTY IS ON THE DEMO LIST. |
| | AN ORDER FROM THE BOARD FOR REPAIRS |
| | MUST |
| | BE GRANTED BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | 9.)PROVIDE MULLION PRODUCT APPROVALS. |
| | |
| | 10.) PROVIDE AREA CALCULATIONS |
| | (EXISTING, PROPOSED, NEW TOTAL).THIS |
| | PROJECT INVOLVES AN ADDITION. |
| | |
| | 11.)PROVIDE ELEVATIONS. |
| | |
| | 12.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 13.)SHEATHING NAILING IS TO COMPLY |
| | WITH CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC TABLE 2306.1.SEE ATTACHED. |
| | |
| | 14.)PROVIDE DESIGN PRESSURES FOR THE |
| | ROOF. |
| | |
| | 15.)FOR THE MODIFIED ROOF, INDICATE |
| | WHICH METHOD OF INSTALLATION YOU ARE |
| | USING. |
| | |
| | 16.)HOW HAVE YOU DETERMINED THE |
| | DESIGN |
| | PRESSURE FOR THE WINDOWS?FBC TABLE |
| | 1606.2B, 140MPH, EXPOSURE B, ZONE 5 |
| | LESS |
| | THAN 10SF HAS A REQUIREMENT OF -47.2. |
| | YOU HAVE DECLARED AN EXPOSURE C, SO THE |
| | NEGATIVE PRESSURE SHOULD BE -67.2. |
| | YOUR |
| | PLAN STATES -44. |
| | |
| | 17.)SPECIFY THE STRAPS.FASTENING |
| | MUST |
| | BE CONSISTENT WITH THE MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | 18.)ALL INFORMATION REQUIRED BY |
| | FAC61G15-23.002 IS TO BE ON THE TITLE |
| | BLOCK.CA NUMBER REQUIRED. |