Plan Review Notes
Plan Review Notes For Permit 04120750
Permit Number 04120750
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-01-07 00:00:001. THE ONLY FIRE HYDRANT SHOWN FOR
 USE IS LOCATED 80 FEET AWAY AND WILL
 BE UTILIZED TO SUPPORT THE FIRE
 DEPARTMENT CONNECTION FOR THE
 REQUIRED FIRE SPRINKLER SYSTEM.
 NO OTHER FIRE HYDRANTS HAVE BEEN
 PROPOSED WHICH IS NOT CORRECT. A
 PRIVATE FIRE HYDRANT IS NEEDED TO
 SUPPORT OPERATIONS IN THE EVENT
 OF A FIRE.
  
 2. WHY IS ONLY ONE FIRE DEPARTMENT
 CONNECTION SHOWN FOR THE THREE
 BUILDINGS. EACH BUILDING SHOULD
 HAVE ITS OWN CONNECTION.
  
 3. REQUIRED FIRE SPRINKLER SYSTEMS
 ARE REQUIRED TO BE MONITORED BY
 A LICENSED LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION
 SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910