| Plan Review Notes For Permit 04120750 |
| Permit Number |
04120750 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-07 00:00:00 | 1. THE ONLY FIRE HYDRANT SHOWN FOR | | | USE IS LOCATED 80 FEET AWAY AND WILL | | | BE UTILIZED TO SUPPORT THE FIRE | | | DEPARTMENT CONNECTION FOR THE | | | REQUIRED FIRE SPRINKLER SYSTEM. | | | NO OTHER FIRE HYDRANTS HAVE BEEN | | | PROPOSED WHICH IS NOT CORRECT. A | | | PRIVATE FIRE HYDRANT IS NEEDED TO | | | SUPPORT OPERATIONS IN THE EVENT | | | OF A FIRE. | | | | | | 2. WHY IS ONLY ONE FIRE DEPARTMENT | | | CONNECTION SHOWN FOR THE THREE | | | BUILDINGS. EACH BUILDING SHOULD | | | HAVE ITS OWN CONNECTION. | | | | | | 3. REQUIRED FIRE SPRINKLER SYSTEMS | | | ARE REQUIRED TO BE MONITORED BY | | | A LICENSED LISTED CENTRAL STATION | | | APPROVED FOR CENTRAL STATION | | | SERVICE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|