| 2004-12-21 00:00:00 | RETURN AIR OUT OF SECOND FLOOR BEDROOM | | | MUST COMPLY WITH 2001 FBC/M 604.1 . | | | | | | RETURN AIR BACK TO A.H.U. IS NOT | | | REFLECTED ON A/C PLAN . | | | | | | CONDENSATE FROM A.H.U. IS NOT REFLECTED | | | ON A/C PLAN . | | | | | | SECONDARY DRAIN PAN UNDER A.H.U. WITH | | | FLOAT S.W. MUST COMPLY WITH 2001 FBC/M | | | 307.2.3.. |
|