Plan Review Notes
Plan Review Notes For Permit 04120665
Permit Number 04120665
Review Stop E
Sequence Number 5
Notes
Date Text
2006-01-18 00:00:00REDLINED PLANS.
 THE GROUNDING ELECTRODE CONDUCTOR WAS
 DECREASED TO A #4 FOR A 300A SERVICE.
 THE MIN AWG SIZE SHALL BE BASED ON THE
 TABLE FROM 31.15B6,250.66. A MIN OF A #2
 IS REQUIRED.