2005-01-05 00:00:00BUILDING PLAN REVIEW FAILED
  
 1.PRIVACY WALL DETAIL ATTACHED TO PLAN
 DOES NOT MATCH THE PRIVACY WALL SHOWN ON
 THE PLAN.
  
 2. DESIGN WIND LOAD : WHICH CODE ARE YOU
 USING TO DETERMINE THE WIND DESIGN (ASCE
 OR FBC CHAPTER 16)
  
 3. PRIVACY WALL DETAIL SHOWS DESIGN WIND
 LOAD @ 90 MPH 3 SEC. GUST1=77 EXB = B
 OPEN. ON PLAN SHEET S1.
  
 4. THE DRAWING ON THE 11 X 17 SHEET
 ATTACHED TO PLAN SHOWS DESIGN WIND LOAD
 @ 90 MPH 3 SEC. GUST, CAT 2 1=1.0. EXP
 B.
  
 5. THE SHEET S1 IS NOT SIGNED & SEALED
 BY ENGINEER.
  
 6. A NOTICE OF COMMENCEMENT MUST BE
 FILED TO THE COUNTY CLERK OFFICE AND A
 COPY OF THE RECORDED NOC SUBMITTED
 BEFORE A PERMIT CAN BE ISSUED.
  
  
  
  
 ANY QUESTIONS PLEASE CALL"
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713