| 2004-12-23 00:00:00 | *********** UNSAT ************ | | | | | | 1)NOTE: PLEASE SUBMIT PLANS SIGNED, | | | DATED AND SEALED BY ENGINEER. | | | PLANS SUBMITTED ARE COPIES WITH CHANGES | | | MADE TO ORIG PLANS. | | | FS 471.025 | | | | | | 2)NOTE: PLEASE SHOW MEANS OF DISC FOR | | | POWER COMING FROM GEN. | | | PLEASE SEE 225.31,32,36 ETC. | | | | | | 3)NOTE: PLEASE SUBMIT MANUFACT SPECS | | | SHEETS FOR ALL NEW EQUIPMENT BEING | | | INSTALLED. | | | | | | 4)NOTE: PLEASE HAVE PLANS CLEARLY SHOW | | | EXISTING AND NEW. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE 230.72 AND GROUPING | | | OF DISC'S AND REQUIRED TO BE IN CLOSE | | | PROXIMITY AS DETERMINED BY AHJ. | | | | | | 6)NOTE: PLEASE SEE COMMENTS FROM OTHER | | | REVIEWERS AS THEY WILL DIRECTLY AFFECT | | | ELECTRICAL PLANS AND PROJECT. | | | | | | MUST PROVIDE SITE PLANS, WIND LOADING, | | | GUARDING OF LIVE PARTS/ENCLOSURE FOR GEN | | | ETC. | | | | | | PLEASE NOTE, DUE TO PLANS AND SUBMITTED | | | PACKAGE NOT BEING COMPLETE AT THIS TIME, | | | THERE MAY BE OTHER COMMENTS TO FOLLOW. | | | | | | | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|