2004-12-23 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SUBMIT PLANS SIGNED,
 DATED AND SEALED BY ENGINEER.
 PLANS SUBMITTED ARE COPIES WITH CHANGES
 MADE TO ORIG PLANS.
 FS 471.025
  
 2)NOTE: PLEASE SHOW MEANS OF DISC FOR
 POWER COMING FROM GEN.
 PLEASE SEE 225.31,32,36 ETC.
  
 3)NOTE: PLEASE SUBMIT MANUFACT SPECS
 SHEETS FOR ALL NEW EQUIPMENT BEING
 INSTALLED.
  
 4)NOTE: PLEASE HAVE PLANS CLEARLY SHOW
 EXISTING AND NEW.
 215.5
  
 5)NOTE: PLEASE SEE 230.72 AND GROUPING
 OF DISC'S AND REQUIRED TO BE IN CLOSE
 PROXIMITY AS DETERMINED BY AHJ.
  
 6)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWERS AS THEY WILL DIRECTLY AFFECT
 ELECTRICAL PLANS AND PROJECT.
  
 MUST PROVIDE SITE PLANS, WIND LOADING,
 GUARDING OF LIVE PARTS/ENCLOSURE FOR GEN
 ETC.
  
 PLEASE NOTE, DUE TO PLANS AND SUBMITTED
 PACKAGE NOT BEING COMPLETE AT THIS TIME,
 THERE MAY BE OTHER COMMENTS TO FOLLOW.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]