Plan Review Notes
Plan Review Notes For Permit 04120601
Permit Number 04120601
Review Stop E
Sequence Number 2
Notes
Date Text
2005-02-11 00:00:00 
  
 PROVISO
 ~~~~~~~
  
 PROVIDE SIGNAGE INDICATING GENERATOR
 DISCONNECT LOCATION WITH THE MAIN
 SERVICE EQUIPMENT.
  
 THE OUTPUT OF THE 25KW GENERATOR IS
 104AMPS. THE LOAD CALC SUBMITTED IS 116
 AMPS. INSTALL AN EMERGENCY PANEL AND
 SELECT LOADS TO CORRELATE WITH GENERATOR
 OUTPUT. RESUMBIT RISER DIAAGRAM SHOWING
 ALL EQUIPMENT AND HOW CONNECTED PRIOR TO
 SCHEDULING FINL ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW