| 2005-02-11 00:00:00 | | | | | | | PROVISO | | | ~~~~~~~ | | | | | | PROVIDE SIGNAGE INDICATING GENERATOR | | | DISCONNECT LOCATION WITH THE MAIN | | | SERVICE EQUIPMENT. | | | | | | THE OUTPUT OF THE 25KW GENERATOR IS | | | 104AMPS. THE LOAD CALC SUBMITTED IS 116 | | | AMPS. INSTALL AN EMERGENCY PANEL AND | | | SELECT LOADS TO CORRELATE WITH GENERATOR | | | OUTPUT. RESUMBIT RISER DIAAGRAM SHOWING | | | ALL EQUIPMENT AND HOW CONNECTED PRIOR TO | | | SCHEDULING FINL ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|