| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | BUILDING REVIEW PROVISO: | | | (PROVIDE REQUIRED INFORMATION PRIOR TO | | | CONSTRUCTION OR INSTALLATION TO AVOID | | | CONFLICTS OR DELAYS). | | | 1- REVISE NAIL SIZE SPECIFIED ON DETAIL | | | 4/4S1. NEED NAIL THAT PROVIDES 1 3/4" | | | MIN. PENETRATION INTO HORIZONTAL FRAMING | | | MEMBER. SEE ASTM C926 AND ASTM C1063. | | | SEC. 2504.2 FBC 2001. | | | | | | 2- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR METAL ROOF. |
|