| Plan Review Notes For Permit 04120576 |
| Permit Number |
04120576 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-20 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} INDICATE CONDUIT & WIRE SIZE & TYPE | | | ON THE EXISTING SERVICE. | | | | | | 2} PLEASE SUBMIT AIC RATINGS FOR ALL NEW | | | SERVICE EQUIPMENT BEING INSTALLED. | | | MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9. | | | | | | 3} THE CONDUCTORS FROM THE METER TO THE | | | PANEL DO NOT COMPLY WITH 310.15(B)(6). | | | ALSO INDICATE CONDUIT TYPE. | | | | | | 4} THE GROUND RODS SHOWN DON'T APPEAR TO | | | BE CONNECTED TO ANYTHING, PLEASE CLARIFY | | | AND INDICATE THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOR. | | | | | | 5} PLEASE PROVIDE A SITE DRAWING | | | INDICATING WHERE ALL THE COMPONENTS OF | | | THE SERNICE ARE LOCATED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|