Plan Review Notes
Plan Review Notes For Permit 04120557
Permit Number 04120557
Review Stop G
Sequence Number 1
Notes
Date Text
2004-12-11 00:00:00GAS PLAN REVIEW,DENIED FBC 2001 FUEL
 GAS
 CODE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE EXISTINGSYSTEM.
 REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34)
 3. MANFACTURES CUT SHEET ON 2LB GAS
 REGULATORS, SHOW LOCATION OF EACH GAS
 REGULATOR.
 END OF COMMENTS QUESTIONS 561-805-6692