| Plan Review Notes For Permit 04120542 |
| Permit Number |
04120542 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-21 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | INDICATE THE SIZE OF THE EXISTING MAIN | | | BREAKER SHOWN ON THE PLAN. | | | | | | SHOW GEC SIZE, CONDUIT AND WIRE SIZES | | | FOR THE SERVICE AND FEEDER. NOTE PLAN | | | SHOWS (3) 9/0. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|