2005-02-08 00:00:00************* UNSAT 2ND REVIEW
 *********
  
 PLEASE SEE NOTES FROM FIRST REVIEW, SOME
 OF WHICH STILL NEED TO BE ADDRESSED AND
 NEW NOTES DUE TO CHANGES IN PLANS.
  
 1)NOTE: NOTE #1, NO, PLEASE SHOW ALL
 CIRCUITING ON PLANS AND CORRELATE WITH
 SUBMITTED PANEL SCHEDULE.
 CIRCUITING MISSING FROM COMMERCIAL
 TENANTS SPACES AND RESIDENTIAL UNIT IS
 COMPLETELY BLANK? 215.5
  
 2)NOTE: NOTE #2 NO, PLEASE SEE 700.12E
 FOR CIRCUITING OF EM/EXT LTS.
  
 3)NOTE: NOTE #3 NO,PLEASE SEE SOME
 TENANT SPACES SHOWN AS MERCHANTILE DO
 NOT INDICATE REQUIRED SIGN CIRCUIT ON
 PLANS PER 600.5.
 PLEASE ALSO SEE 210.62,220.12, SHOW
 WINDOW RECEPTS ARE NOT PERMITTED TO HAVE
 OTHER GENERAL USE RECEPTS ON THE SAME
 CIRCUIT.
  
 4)NOTE: NOTE#4 NO, PLEASE SEE A RISER IS
 SHOWN, HOWEVER NO WIRE SIZES ARE
 INDICATED ON PANEL SCHEDULES FOR BRANCH
 CIRCUIT WIRING???
 PLEASE SEE PANEL SCHEDULES DO NOT
 INDICATE ANY OVERCURRENT PROTECTION
 SIZES FOR BRANCH CIRCUITS?
 240.4,310.16,215.5
 PLEASE ALSO SEE PANEL SCHEDULE FOR
 RESIDENTIAL UNIT ONLY SHOWS A/C UNIT,
 YET LOAD CALCULATION DO NOT CORRELATE?
 215.5
 PLEASE SEE GROUNDING ELECTRODE SYSTEM TO
 BE SHOWN PER 250.50. CWP?
 PLEASE VERIFY WHY RESIDENTIAL UNIT WHICH
 IS PART OF THIS BLDG, IS SHOWN WITH A
 SEPARATE SERVICE? PLEASE SEE 230.2 FOR
 ADDITIONAL SERVICES PERMITTED.
  
 4)NOTE: NOTE #4, NO, PLEASE SEE 2002
 NEC.
  
 **************************************
 PLEASE SEE NEW COMMENTS DUE TO CHANGES
 IN PLANS.
  
 1)NOTE: PLEASE SEE COND UNITS ARE FOR
 EACH SPACE IS NOW SHOWN INSIDE ONE OF
 THE TENANT SPACES STORAGE RMS?
 THIS IS NOT PERMITTED AND PLEASE SEE ANY
 MECHANICAL COMMENTS FOR LOCATION OF
 UNITS ALSO.
  
 2)NOTE: PLEASE SEE RESIDENTIAL LOAD
 CALCS INDICATE A WASHER AND A LAUNDRY
 CIRCUIT? PLEASE VERIFY. PLEASE ALSO SEE
 220.16 FOR A MIN OF 1500VA
  
 3)NOTE: PLEASE SEE 220.19 FOR MIN LOAD
 FOR RANGES TO BE FIGURED IN A
 RESIDENTIAL UNIT.
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 PLEASE ALSO SEE 220.12 FOR SHOW WINDOW
 LOADS.
 215.3,230.42, ETC
  
 5)NOTE: PLEASE SHOW ALL MIN REQUIRED FOR
 RESIDENTIAL UNIT, RECEPTS,LTS, SWITCHES,
 SD'S ETCPER 2002 NEC
 210.52,210.70,210.11, ETC
 NFPA-72 8-1.4.1.6.2 AND 8-1.4.2 FOR SD
 PLACEMENT.
  
 6)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS FOR REVIEW AND STAMPING.
 PLEASE SEE ONE SET HAD AN E-1 AND THE
 OTHER HAD AN E-2?
  
 7)NOTE: PLEASE SEE PLANS NOW INDICATE
 BEING DRAWN BY BRAUN ELECTRIC, HOWEVER
 PLANS ARE STILL SHOWN AS SIGNED AND
 SEALED BY GORDON BUCK( STRUCTUAL
 ENGINEER)? PLEASE SEEPLANS ARE TO HAVE
 THE PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS. FBC 104.2.1
 PLEASE SEE ONE SET OF ORIGINAL PLANS AND
 THE ONE SET SUBMITTED FOR THIS REVIEW IS
 BEING RETAINED AND SHALL BE TURNED INTO
 THE FBPE'S FOR REVIEW.
 PLEASE ALSO SEE COPY OF FS. 553.80(2)(B)
 WHICH IS NOW ATTACHED AND GIVEN AS
 NOTICE AT THIS TIME. THE WILL BE
 ACCESSED IF PLANS COME BACK WITH ANY OF
 THE SAME COMMENTS NOT ADDRESSED FOR
 THIRD REVIEW.
  
 8)NOTE:PLEASE SEE FBC 104.6.5 FOR
 VALUATION OF SCOPE OF WORK INDICATED ON
 PLANS.
 PLEASEPROVIDE A COPY OF CONTRACTS FOR
 WORK PROPOSED. VALUE SHOWN AS
 $12,800.00
  
 PLEASE REMOVEV ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE SEE BLDG REVIEW
 COMMENTS ON FIRST REVIEW.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]