| 2005-02-08 00:00:00 | ************* UNSAT 2ND REVIEW |
| | ********* |
| | |
| | PLEASE SEE NOTES FROM FIRST REVIEW, SOME |
| | OF WHICH STILL NEED TO BE ADDRESSED AND |
| | NEW NOTES DUE TO CHANGES IN PLANS. |
| | |
| | 1)NOTE: NOTE #1, NO, PLEASE SHOW ALL |
| | CIRCUITING ON PLANS AND CORRELATE WITH |
| | SUBMITTED PANEL SCHEDULE. |
| | CIRCUITING MISSING FROM COMMERCIAL |
| | TENANTS SPACES AND RESIDENTIAL UNIT IS |
| | COMPLETELY BLANK? 215.5 |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE 700.12E |
| | FOR CIRCUITING OF EM/EXT LTS. |
| | |
| | 3)NOTE: NOTE #3 NO,PLEASE SEE SOME |
| | TENANT SPACES SHOWN AS MERCHANTILE DO |
| | NOT INDICATE REQUIRED SIGN CIRCUIT ON |
| | PLANS PER 600.5. |
| | PLEASE ALSO SEE 210.62,220.12, SHOW |
| | WINDOW RECEPTS ARE NOT PERMITTED TO HAVE |
| | OTHER GENERAL USE RECEPTS ON THE SAME |
| | CIRCUIT. |
| | |
| | 4)NOTE: NOTE#4 NO, PLEASE SEE A RISER IS |
| | SHOWN, HOWEVER NO WIRE SIZES ARE |
| | INDICATED ON PANEL SCHEDULES FOR BRANCH |
| | CIRCUIT WIRING??? |
| | PLEASE SEE PANEL SCHEDULES DO NOT |
| | INDICATE ANY OVERCURRENT PROTECTION |
| | SIZES FOR BRANCH CIRCUITS? |
| | 240.4,310.16,215.5 |
| | PLEASE ALSO SEE PANEL SCHEDULE FOR |
| | RESIDENTIAL UNIT ONLY SHOWS A/C UNIT, |
| | YET LOAD CALCULATION DO NOT CORRELATE? |
| | 215.5 |
| | PLEASE SEE GROUNDING ELECTRODE SYSTEM TO |
| | BE SHOWN PER 250.50. CWP? |
| | PLEASE VERIFY WHY RESIDENTIAL UNIT WHICH |
| | IS PART OF THIS BLDG, IS SHOWN WITH A |
| | SEPARATE SERVICE? PLEASE SEE 230.2 FOR |
| | ADDITIONAL SERVICES PERMITTED. |
| | |
| | 4)NOTE: NOTE #4, NO, PLEASE SEE 2002 |
| | NEC. |
| | |
| | ************************************** |
| | PLEASE SEE NEW COMMENTS DUE TO CHANGES |
| | IN PLANS. |
| | |
| | 1)NOTE: PLEASE SEE COND UNITS ARE FOR |
| | EACH SPACE IS NOW SHOWN INSIDE ONE OF |
| | THE TENANT SPACES STORAGE RMS? |
| | THIS IS NOT PERMITTED AND PLEASE SEE ANY |
| | MECHANICAL COMMENTS FOR LOCATION OF |
| | UNITS ALSO. |
| | |
| | 2)NOTE: PLEASE SEE RESIDENTIAL LOAD |
| | CALCS INDICATE A WASHER AND A LAUNDRY |
| | CIRCUIT? PLEASE VERIFY. PLEASE ALSO SEE |
| | 220.16 FOR A MIN OF 1500VA |
| | |
| | 3)NOTE: PLEASE SEE 220.19 FOR MIN LOAD |
| | FOR RANGES TO BE FIGURED IN A |
| | RESIDENTIAL UNIT. |
| | |
| | 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | ARE TO BE SHOWN AT 125%. |
| | PLEASE ALSO SEE 220.12 FOR SHOW WINDOW |
| | LOADS. |
| | 215.3,230.42, ETC |
| | |
| | 5)NOTE: PLEASE SHOW ALL MIN REQUIRED FOR |
| | RESIDENTIAL UNIT, RECEPTS,LTS, SWITCHES, |
| | SD'S ETCPER 2002 NEC |
| | 210.52,210.70,210.11, ETC |
| | NFPA-72 8-1.4.1.6.2 AND 8-1.4.2 FOR SD |
| | PLACEMENT. |
| | |
| | 6)NOTE: PLEASE SUBMIT TWO COMPLETE SETS |
| | OF PLANS FOR REVIEW AND STAMPING. |
| | PLEASE SEE ONE SET HAD AN E-1 AND THE |
| | OTHER HAD AN E-2? |
| | |
| | 7)NOTE: PLEASE SEE PLANS NOW INDICATE |
| | BEING DRAWN BY BRAUN ELECTRIC, HOWEVER |
| | PLANS ARE STILL SHOWN AS SIGNED AND |
| | SEALED BY GORDON BUCK( STRUCTUAL |
| | ENGINEER)? PLEASE SEEPLANS ARE TO HAVE |
| | THE PRINTED NAME AND SIGNATURE OF PERSON |
| | RESPONSIBLE FOR PLANS. FBC 104.2.1 |
| | PLEASE SEE ONE SET OF ORIGINAL PLANS AND |
| | THE ONE SET SUBMITTED FOR THIS REVIEW IS |
| | BEING RETAINED AND SHALL BE TURNED INTO |
| | THE FBPE'S FOR REVIEW. |
| | PLEASE ALSO SEE COPY OF FS. 553.80(2)(B) |
| | WHICH IS NOW ATTACHED AND GIVEN AS |
| | NOTICE AT THIS TIME. THE WILL BE |
| | ACCESSED IF PLANS COME BACK WITH ANY OF |
| | THE SAME COMMENTS NOT ADDRESSED FOR |
| | THIRD REVIEW. |
| | |
| | 8)NOTE:PLEASE SEE FBC 104.6.5 FOR |
| | VALUATION OF SCOPE OF WORK INDICATED ON |
| | PLANS. |
| | PLEASEPROVIDE A COPY OF CONTRACTS FOR |
| | WORK PROPOSED. VALUE SHOWN AS |
| | $12,800.00 |
| | |
| | PLEASE REMOVEV ALL OLD/VOIDED SHEETS |
| | FROM SETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. PLEASE SEE BLDG REVIEW |
| | COMMENTS ON FIRST REVIEW. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |