2005-01-10 00:00:00DENIED;
 1.NOT ENOUGH INFORMATION TO DO A
 PLUMBING REVIEW. PLEASE SHOW RISER
 DIAGRAMS FOR SANITARY AND WATER. SHOW
 HOW RAIN IS DISCHARGED FROM FLAT ROOF
 AREA.
 2.DRINKING FOUNTAINS ARE REQUIRED TO
 MEET MINIMUM PLUMBING FACILITIES. SEE
 FBC PLUMGBING TABLE 403.1.
 3.OFFICE SPACE C & D. BATHROOM
 FACILITIES SHALL BE EATHER SEPARATE OR
 PUBLIC CUSTOMER FACILITIES. SEC.403.5