| Plan Review Notes For Permit 04120533 |
| Permit Number |
04120533 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-01-10 00:00:00 | DENIED; | | | 1.NOT ENOUGH INFORMATION TO DO A | | | PLUMBING REVIEW. PLEASE SHOW RISER | | | DIAGRAMS FOR SANITARY AND WATER. SHOW | | | HOW RAIN IS DISCHARGED FROM FLAT ROOF | | | AREA. | | | 2.DRINKING FOUNTAINS ARE REQUIRED TO | | | MEET MINIMUM PLUMBING FACILITIES. SEE | | | FBC PLUMGBING TABLE 403.1. | | | 3.OFFICE SPACE C & D. BATHROOM | | | FACILITIES SHALL BE EATHER SEPARATE OR | | | PUBLIC CUSTOMER FACILITIES. SEC.403.5 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|