Plan Review Notes For Permit 04120533
Permit Number 04120533
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-02-23 00:00:001. NO SMOKE DETECTORS SHOWN IN
 APARTMENT. ELECTRIC POWERED
 SMOKE DETECTORS ARE REQUIRED INSIDE
 AND OUTSIDE OF EVERY SLEEPING ROOM.
  
 2. BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6"
 HIGH NUMBERS ARE REQUIRED.
  
 3. NO HANDRAIL (S) SHOWN FOR
 INTERIOR STAIR.
  
 4. THE FIRST FLOOR LEVEL MUST
 MEET ALL OF THE CODE REQUIREMENTS
 FOR MERCANTILE OCCUPANCIES. PROPER
 TENANT SEPARATIONS, OPENING
 PROTECTIVES, PORTABLE FIRE
 EXTINGUISHERS, EMERGENCY LIGHTS
 AND EXIT SIGNS ARE REQUIRED.
 PROPER DOOR LOCKS ARE REQUIRED.
 THE FIRST FLOOR IMPROVEMENTS ARE
 SUBJECT TO FIELD INSPECTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910
  
 APPROVED PROVISO:
2004-12-27 00:00:001. BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6"
 HIGH NUMBERS ARE REQUIRED.
  
 2. PLEASE INDICATE ALL HORIZONTAL
 AND VERTICAL FIRE SEPARATIONS BETWEEN
 DIFFERENT TENANTS AND DIFFERENT
 OCCUPANCY TYPES. ALSO PLEASE
 SHOW REQUIRED OPENING PROTECTIVES.
  
 3. IT APPEARS THAT AN EXIT SIGN FOR
 OFFICE/RETAIL B MAY BE LOCATED INFRONT
 OF A GARAGE DOOR.
  
 4. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR ALL WALLS AND
 CEILINGS.
  
 5. HOW IS STAIR SEPARATED FROM
 REMAINDER OF BUILDING.
  
 6. NO DOOR SCHEDULE PROVIDED.
  
 7. NO FIRE SAFING DETAILS PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910