| Plan Review Notes For Permit 04120533 |
| Permit Number |
04120533 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-27 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLEASE PROVIDE ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH PANEL SCHEDULES | | | TO BE SUBMITTED. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE 2002 NEC FOR MIN | | | CIRCUITING REQUIRED. | | | 700.12E | | | | | | 3)NOTE: PLEASE SEE 600.5, 210.62, 220.12 | | | FOR MIN REQUIRED. | | | | | | 4)NOTE: PLEASE SUBMIT A COMPLETED RISER | | | DIAGRAM SHOWING NEW SERVICE. PLEASE SEE | | | MAINS ARE TO BE GROUPED. 230.72. | | | SHOW CONDUCTOR SIZES, CONDUITS, | | | GROUNDING FOR NEW SERVICE. ETC. | | | 215.5,310.16,240.4,250.50 ETC. | | | | | | | | | 5)NOTE: PLANS APPEAR TO SHOW MIXED USE | | | OCCP. PLEASE ADJUST ELECTRICAL PLANS. | | | PLEASE SEE 2002 NEC FOR ALL MIN REQUIRED | | | FOR RESIDENTIAL. | | | | | | PLEASE NOTE: DUE TO PLANS NOT BEING | | | COMPLETE AT THIS TIME, A COMPLETE REVIEW | | | FOR CODE COMPLIANCE CAN NOT BE DONE. | | | | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | | AFFECT ON ELECTRICAL PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|