2004-12-27 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULES
 TO BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE 2002 NEC FOR MIN
 CIRCUITING REQUIRED.
 700.12E
  
 3)NOTE: PLEASE SEE 600.5, 210.62, 220.12
 FOR MIN REQUIRED.
  
 4)NOTE: PLEASE SUBMIT A COMPLETED RISER
 DIAGRAM SHOWING NEW SERVICE. PLEASE SEE
 MAINS ARE TO BE GROUPED. 230.72.
 SHOW CONDUCTOR SIZES, CONDUITS,
 GROUNDING FOR NEW SERVICE. ETC.
 215.5,310.16,240.4,250.50 ETC.
  
  
 5)NOTE: PLANS APPEAR TO SHOW MIXED USE
 OCCP. PLEASE ADJUST ELECTRICAL PLANS.
 PLEASE SEE 2002 NEC FOR ALL MIN REQUIRED
 FOR RESIDENTIAL.
  
 PLEASE NOTE: DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, A COMPLETE REVIEW
 FOR CODE COMPLIANCE CAN NOT BE DONE.
  
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  