2005-01-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120533
 ADD: 4912 S DIXIE HWY
 CONT: ADAM PLASTERING
 TEL: (561248-5400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2*
 ADDITIONAL INFORMATION REQUIRED,
 2A) 704.3 INDICATE, TENANT SEPERATION
 PROVIDE U.L. LISTING OR GYPSUM
 ASSOCIATION NUMBER.
 2B)TABLE 704.1 OCCUPANCY SEPERATION,
 PROVIDE INFORMATION INDICATING
 COMPLIANCE.
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) EXTERIOR DOORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4) 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.
  
 5) NOTE THE GLAZING BEING REPLACED ON
 EXISTING BUILDINGS WILL NEED TO MEET THE
  
 REQUIREMENTS FOR LARGE MISSLE IMPACT
 SEE
 3401.7.2.4. ONLY IF THIS WAS A 1 OR 2
 FAMILY DWELLING IS THERE A 25%
 EXCEPTION.
  
 6) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 7) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 WHAT IS THE AREA JUST LEFT ON THE
 STAIRWELL FOR THE FIRST FLOOR? IS THIS
 INTERIOR / EXTERIOR? WHAT WILL THIS AREA
 BE USED FOR?
  
 8) ELECTRIC PLAN INDICATES OFFICE "A"
 INDICATES A ON 2 EAST WALLS BUT NO
 REFRENCE TO WHAT THIS IS FOR? OFFICE
 "B" ALSO HAS A SIMILAR SITUATION?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026