2005-12-14 00:00:00****** UNSAT *****
  
 PLEASE SEE SOME ITEMS FROM PREVIOUSLY
 REDLINED PLANS AND SOME NEW ITEMS DUE TO
 CHANGES IN SCOPE OF WORK NEED TO BE
 CORRECTED.
  
  
 1)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 2)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52C1
  
 3)NOTE: PLEASE NOW SEE A DINING ROOM GFI
 IS NOW ON WITH THE BATH GFI CIRCUIT
 WHICH IS NOT PERMITTED.
 PLEASE SEE 210.52D AND 210.11C3 WHICH
 DOES NOT PERMIT ANY OTHER AREA RECEPTS
 ON WITH THE BATH DEDICATED 20A CIRCUIT.
  
 4)NOTE: PLEASE ALSO NOW SEE ITEM WHICH
 WAS REDLINEDORIGINALLY. PLEASE SEE
 SD'S ARE SHOWN ON WITH BATH LIGHTING
 CIRCUIT, THIS IS OK, HOWEVER THIS
 CIRCUIT IS NOW REQUIRED TO BE AFCI
 PROTECTED AS THE 2002 NEC 210.12
 REQUIRES ALL "OUTLETS" IN BEDRMS TO BE
 ARC FAULT PROTECTED.
  
 5)NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH
 REQUIRES SD'S TO BE A MIN OF 3' FROM ANY
 BATH DOORS.
  
 6)NOTE: PLEASE LIST THE MIN REQUIRED AWG
 ON PANEL SCHEDULE. PLEASE SEE 240.4,
 310.16
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  