| Plan Review Notes For Permit 04120512 |
| Permit Number |
04120512 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-12-14 00:00:00 | ****** UNSAT ***** | | | | | | PLEASE SEE SOME ITEMS FROM PREVIOUSLY | | | REDLINED PLANS AND SOME NEW ITEMS DUE TO | | | CHANGES IN SCOPE OF WORK NEED TO BE | | | CORRECTED. | | | | | | | | | 1)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52C1 | | | | | | 3)NOTE: PLEASE NOW SEE A DINING ROOM GFI | | | IS NOW ON WITH THE BATH GFI CIRCUIT | | | WHICH IS NOT PERMITTED. | | | PLEASE SEE 210.52D AND 210.11C3 WHICH | | | DOES NOT PERMIT ANY OTHER AREA RECEPTS | | | ON WITH THE BATH DEDICATED 20A CIRCUIT. | | | | | | 4)NOTE: PLEASE ALSO NOW SEE ITEM WHICH | | | WAS REDLINEDORIGINALLY. PLEASE SEE | | | SD'S ARE SHOWN ON WITH BATH LIGHTING | | | CIRCUIT, THIS IS OK, HOWEVER THIS | | | CIRCUIT IS NOW REQUIRED TO BE AFCI | | | PROTECTED AS THE 2002 NEC 210.12 | | | REQUIRES ALL "OUTLETS" IN BEDRMS TO BE | | | ARC FAULT PROTECTED. | | | | | | 5)NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH | | | REQUIRES SD'S TO BE A MIN OF 3' FROM ANY | | | BATH DOORS. | | | | | | 6)NOTE: PLEASE LIST THE MIN REQUIRED AWG | | | ON PANEL SCHEDULE. PLEASE SEE 240.4, | | | 310.16 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|