Plan Review Notes
Plan Review Notes For Permit 04120512
Permit Number 04120512
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-16 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS MENTION TO
 CHANGE OUT PANEL, YET NO INFORMATION IS
 PROVIDED FOR THIS.
 SIZE? CONDUCTORS? MB? ETC.
 215.5
  
 2)NOTE: PLEASE SEE 210.52D,210.11C3,
 BATHS TO BE 20A, #12.
  
 3)NOTE: PLEASE SEE 2002 210.12 FOR ARC
 FAULT PROTECTION OF NEW ELECTRICAL IN
 BEDRMS.
  
 4)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 GFI RECEPTS ALONG KITCHEN COUNTERSPACE.
 NEW ? OR EXSITING?
  
 5)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE FOR NEW CIRCUITS BEING
 INSTALLED.215.5
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  