Plan Review Notes
Plan Review Notes For Permit 04120512
Permit Number 04120512
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04120512
 ADD: 1701 S FLAGLER DR # 1807
 CONT:PROJECT ONE INTERIORS
 TEL: (561)541-4555
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-1 DEMO NOTES CORRECT THE
 MUNICIPALITY NOT PALM BEACH.
  
 3) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) SLIDING DOORS
  
 4) PRESSURES ARE TO REFLECT THAT OF A 18
 STORY BUILDING "C" ZONE, FOR A
 ZONE 5 (END ZONE) -139.
  
 REVIEW BY JIM WITMER
 (561) 805-6715
 FAX (561) 653-2692
 E-MAIL [email protected]