| Plan Review Notes For Permit 04120452 |
| Permit Number |
04120452 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-10 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR ALL NEW | | | SERVICE EQUIPMENT BEING INSTALLED. | | | MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9. | | | | | | 2} INDICATE THE GROUNDING ELECTRODE | | | CONDUCTOR SIZE PER 250.66. | | | | | | 3} INDICATE SIZE & TYPE OF CONDUIT USED | | | FOR RISER AND NIPPLE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|