| 2005-09-28 00:00:00 | PERMIT:04120431 |
| | ADD: 333 EVERNIA |
| | CONT: SCHNELL CONSTRUCTION |
| | TEL: (941)321-1915 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1) QUESTION # 1 FROM THE PREVIOUS REVIEW |
| | ASK FOR THE MINIMUM BUILDING TYPE? |
| | |
| | 3401.7.2.3 NON-STRUCTURAL REPAIRS AND |
| | ALTERATIONS EXCLUSIVE OF FIXTURES AND |
| | FURNITURE, THE COST OF WHICH DOES NOT |
| | EXCEED 25 PERCENT OF THE VALUE OF THE |
| | EXISTING BUILDING OR STRUCTURE AND WHICH |
| | DO NOT AFFECT EGRESS OR FIRE |
| | RESISTIVITY, MAY BE MADE OF THE SAME |
| | MATERIAL OF WHICH THE BUILDING OR |
| | STRUCTURE IS CONSTRUCTED. |
| | THE KEY WORDS "FIRE RESISTANCY" ARE |
| | THE FACTORS WE ARE CONCERNED WITH.THIS |
| | BUILDING IS A TYPE IV BUILDING DESIGNED |
| | UNDER THE SBC AT 110 MPH (FASTEST MILE). |
| | THE FIRE RESISTANCY WE SPEAK OF HAS BEEN |
| | IN CHAPTER 26 SINCE AT LEAST 1982.EFIS |
| | SYSTEMS ARE A COMBUSSTIBLE AND ARETO BE |
| | TESTED TO ASTM E 119. THEY ALSO NEED TO |
| | BE TESTED FOR COMPLIANCE FOR WIND. UNDER |
| | THE SBC YEAR 1982 TABLE 1205.1 FASTEST |
| | MILE PRESSURE WOULD BE - 40 FOR |
| | BUILDINGS 50-100'. THIS WOULD TRANSLATE |
| | TO THE CURRENT CODE 140 MILES PER HR AND |
| | THE -36.7 FOR 100" EFFECTIVE WIND AREA. |
| | |
| | EITHER UNDER THE CODE THE BUILDING WAS |
| | DESIGNED OR CURRENT CODE, PRODUCT |
| | APPROVALS FOR FIRE RESISTANCY AS WELL AS |
| | WIND TABLE 1205.1 82 CODE OR 1606.2 B |
| | UNDER THE CURRENT 2001 FL B CODE WILL |
| | REQUIRE PRODUCT APPROVALS. |
| | |
| | THE FL COVERSHEET FOR THE STO EFIS |
| | SYSTEM IS REQUIRED BUT THE CONTRACTOR |
| | STILL HAS NOT SUBMITTED THE BACKUP |
| | REPORT. THE ARCHITECT EVEN SPECIFIES |
| | THAT STO HI-CM EFIS SYSTEM IS TO BE |
| | USED.THE CONTRACTOR IS TO SUPPLY (2) |
| | COPIES OF THE MIAMI-DADE REPORT. THIS |
| | REPORT INDICATES WHAT PRESSURES IT IS |
| | DESIGNED FOR. |
| | |
| | 2) COMMENT # 2 FROM THE PREVIOUS |
| | REVIEW. DEALS WITH THE PRE-MANUFACTURED |
| | ATTENDANT BOOTH, THIS STRUCTURE IS |
| | COVERED A MANUFACTURED BUILDING COVERED |
| | UNDER DEPARTMENT OF COMMUNITY AFFAIRS. |
| | THESE ARE STATE APPROVED PLANS, PROVIDE |
| | COPIES OF THESE PLANS INDICATING THAT IT |
| | COMPLIES WITH 140 MPH WIND ZONE.RULE |
| | 9B-1 MANUFACTUREED BUILDINGS, FL S S 553 |
| | PART (1).PROVIDE THE 14 SHEETS THAT ARE |
| | A PART OF THE STATE APPROVED PLANS. |
| | PAGE 8 WILL SHOW THE ATTACHMENT DETAILS |
| | TO THE FOUNDATION (SLAB). |
| | |
| | 3)NOTE!!! THIS IS A COMMENT THAT DEALS |
| | WITH THE ATTENDANTS BOOTH, THE BOOTH |
| | DOES HAVE TO BE HANDICAPPED ACCESSIBLE |
| | PROVIDE DETAILS INDICATING ACCESSIBILITY |
| | INTO THE BOOTH.STATE PLANS SHOULD SHOW |
| | RAMPAGE TO BOOTH.ACCESSIBILE ROUTE TO |
| | ALTERED AREAS. |
| | HIGHLIGHT WHICH TYPE OF BOOTH TO BE |
| | USED, SIDE ENTRANCE OR REAR ENTRANCE FOR |
| | |
| | ACCESSIBILTY. |
| | |
| | 11-4.1.6(2) DUTY TO |
| | PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO |
| | ALTERED AREAS SHALL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL |
| | ALTERATION WHEN THE COST EXCEEDS 20 % OF |
| | THE COST OF THE ALTERA- TION TO THE |
| | PRIMARY FUNCTION AREA.(A)(I) AN |
| | ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | |