Plan Review Notes
Plan Review Notes For Permit 04120431
Permit Number 04120431
Review Stop B
Sequence Number 3
Notes
Date Text
2005-09-28 00:00:00PERMIT:04120431
 ADD: 333 EVERNIA
 CONT: SCHNELL CONSTRUCTION
 TEL: (941)321-1915
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
  
 1) QUESTION # 1 FROM THE PREVIOUS REVIEW
 ASK FOR THE MINIMUM BUILDING TYPE?
  
 3401.7.2.3 NON-STRUCTURAL REPAIRS AND
 ALTERATIONS EXCLUSIVE OF FIXTURES AND
 FURNITURE, THE COST OF WHICH DOES NOT
 EXCEED 25 PERCENT OF THE VALUE OF THE
 EXISTING BUILDING OR STRUCTURE AND WHICH
 DO NOT AFFECT EGRESS OR FIRE
 RESISTIVITY, MAY BE MADE OF THE SAME
 MATERIAL OF WHICH THE BUILDING OR
 STRUCTURE IS CONSTRUCTED.
 THE KEY WORDS "FIRE RESISTANCY" ARE
 THE FACTORS WE ARE CONCERNED WITH.THIS
 BUILDING IS A TYPE IV BUILDING DESIGNED
 UNDER THE SBC AT 110 MPH (FASTEST MILE).
 THE FIRE RESISTANCY WE SPEAK OF HAS BEEN
 IN CHAPTER 26 SINCE AT LEAST 1982.EFIS
 SYSTEMS ARE A COMBUSSTIBLE AND ARETO BE
 TESTED TO ASTM E 119. THEY ALSO NEED TO
 BE TESTED FOR COMPLIANCE FOR WIND. UNDER
 THE SBC YEAR 1982 TABLE 1205.1 FASTEST
 MILE PRESSURE WOULD BE - 40 FOR
 BUILDINGS 50-100'. THIS WOULD TRANSLATE
 TO THE CURRENT CODE 140 MILES PER HR AND
 THE -36.7 FOR 100" EFFECTIVE WIND AREA.
  
 EITHER UNDER THE CODE THE BUILDING WAS
 DESIGNED OR CURRENT CODE, PRODUCT
 APPROVALS FOR FIRE RESISTANCY AS WELL AS
 WIND TABLE 1205.1 82 CODE OR 1606.2 B
 UNDER THE CURRENT 2001 FL B CODE WILL
 REQUIRE PRODUCT APPROVALS.
  
 THE FL COVERSHEET FOR THE STO EFIS
 SYSTEM IS REQUIRED BUT THE CONTRACTOR
 STILL HAS NOT SUBMITTED THE BACKUP
 REPORT. THE ARCHITECT EVEN SPECIFIES
 THAT STO HI-CM EFIS SYSTEM IS TO BE
 USED.THE CONTRACTOR IS TO SUPPLY (2)
 COPIES OF THE MIAMI-DADE REPORT. THIS
 REPORT INDICATES WHAT PRESSURES IT IS
 DESIGNED FOR.
  
 2) COMMENT # 2 FROM THE PREVIOUS
 REVIEW. DEALS WITH THE PRE-MANUFACTURED
 ATTENDANT BOOTH, THIS STRUCTURE IS
 COVERED A MANUFACTURED BUILDING COVERED
 UNDER DEPARTMENT OF COMMUNITY AFFAIRS.
 THESE ARE STATE APPROVED PLANS, PROVIDE
 COPIES OF THESE PLANS INDICATING THAT IT
 COMPLIES WITH 140 MPH WIND ZONE.RULE
 9B-1 MANUFACTUREED BUILDINGS, FL S S 553
 PART (1).PROVIDE THE 14 SHEETS THAT ARE
 A PART OF THE STATE APPROVED PLANS.
 PAGE 8 WILL SHOW THE ATTACHMENT DETAILS
 TO THE FOUNDATION (SLAB).
  
 3)NOTE!!! THIS IS A COMMENT THAT DEALS
 WITH THE ATTENDANTS BOOTH, THE BOOTH
 DOES HAVE TO BE HANDICAPPED ACCESSIBLE
 PROVIDE DETAILS INDICATING ACCESSIBILITY
 INTO THE BOOTH.STATE PLANS SHOULD SHOW
 RAMPAGE TO BOOTH.ACCESSIBILE ROUTE TO
 ALTERED AREAS.
 HIGHLIGHT WHICH TYPE OF BOOTH TO BE
 USED, SIDE ENTRANCE OR REAR ENTRANCE FOR
  
 ACCESSIBILTY.
  
 11-4.1.6(2) DUTY TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO
 ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERA- TION TO THE
 PRIMARY FUNCTION AREA.(A)(I) AN
 ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026