2004-12-15 00:00:001. EMERGENCY LIGHTING AND ILLUMINATED
 EXIT SIGNS SHALL COMPLY WITH
 CHAPTER SEVEN, MEANS OF EGRESS,
 LIFE SAFETY CODE, 2000 EDITION.
  
 2. NO PENETRATIONS ALLOWED WITHIN
 ANY EXIT STAIRS. TOWER # 2 PARTIAL
 GROUND LEVEL FLOOR PLAN.
  
 3. PARKING GARAGE TO COMPLY WITH
 NFPA 88A.
  
 4. REPAIRS FOR CRACKS NEAR STAIRTOWERS
 SHALL NOT INTERFERE WITH ANY ABILITY
 TO EXIT.
  
 5. NO PRODUCT INFORMATION REGARDING
 THE PROPOSED GENERATOR.
  
 6. ANY ROOMS OPENING DIRECTLY
 ONTO EXIT STAIRTOWERS ARE TO BE
 PROPERLY RATED.
  
 7. WILL THE EXISTING FIRE PUMP
 BE CONNECTED TO THE NEW PROPOSED
 GENERATOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910