Plan Review Notes
Plan Review Notes For Permit 04120385
Permit Number 04120385
Review Stop P
Sequence Number 3
Notes
Date Text
2005-03-26 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A2 SANT. RISER DIAGRAM DOES NOT
 MEET CODE REQUIREDMENTS. THE TUB IS NOT
 VENTED. SECTION 901.2.1. (SEE RED LINE
 CORRECTION ON ONE SET OF PLANS SHOWING
 EXAMPLE OF RISER THAT MEETS CODE)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721