| 2005-01-25 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE COUNTERTOP RECEPTACLE SPACING | | | DOES NOT COMPLY WITH 210.52(C)(1) AND | | | 210.52(C)(3). SEE "EXCEPTION". | | | | | | 2} THE PANEL SCHEDULE, RISER AND LOAD | | | CALCSMUST BE SUBMITTED BY THE ENGINEER | | | OF RECORD PER 471.025 FL STATUTES. ALSO | | | NOTE THE FOLLOWING COMMENTS ON THE | | | SUBMITTED SET ( AND SEE REVIEWED PLAN). | | | A)DISHWASHER,DISPOSAL,MICROWAVE AND | | | POOL PUMP ON THE SCHEDULE DO NOT APPEAR | | | IN THE CALCS. | | | B) NOT ALL OCP'S LISTED ON SCHED. | | | C) NO AIC RATING FOR EQUIPMENT ON | | | RISER, 110.9. | | | | | | 3} THE BEDROOM RECEPTACLE SPACING STILL | | | DOES NOT COMPLY WITH 210.52(A). | | | | | | 4} PLEASE NOTE SMOKE DETECTOR OUTSIDE | | | BATH DOOR MUST MAINTAIN 3' CLEARANCE PER | | | 8-4.1.2 NFPA-72. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|