 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE COUNTERTOP RECEPTACLE SPACING
 DOES NOT COMPLY WITH 210.52(C)(1) AND
 210.52(C)(3). SEE "EXCEPTION".
  
 2} THE PANEL SCHEDULE, RISER AND LOAD
 CALCSMUST BE SUBMITTED BY THE ENGINEER
 OF RECORD PER 471.025 FL STATUTES. ALSO
 NOTE THE FOLLOWING COMMENTS ON THE
 SUBMITTED SET ( AND SEE REVIEWED PLAN).
 A)DISHWASHER,DISPOSAL,MICROWAVE AND
 POOL PUMP ON THE SCHEDULE DO NOT APPEAR
 IN THE CALCS.
 B) NOT ALL OCP'S LISTED ON SCHED.
 C) NO AIC RATING FOR EQUIPMENT ON
 RISER, 110.9.
  
 3} THE BEDROOM RECEPTACLE SPACING STILL
 DOES NOT COMPLY WITH 210.52(A).
  
 4} PLEASE NOTE SMOKE DETECTOR OUTSIDE
 BATH DOOR MUST MAINTAIN 3' CLEARANCE PER
 8-4.1.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  