2004-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIEMENTS, NOR REFLECT THE FLOOR
 PLAN.
 A) THE W/M SHALL BE VENTED. SECTION
 901.2.1
 B) CLEAN OUT REQUIRED ON W/M STACK 4'
 ABOVE THE FLOOR. SECTION 708.10
 C) SHOW PIPING IN SLAB AT BATHROOM. AS
 DRAWN THE PIPING WILL REQUIRE C/O'S EACH
 TIME IT ENTERS THE BLDG. SECTION
 708.3.5
 D) BRANCH DRAIN INTO THE BATHROOM IS
 SHOWN AS 2". MINIMUM 3" REQUIRED.
 E) SEE RED LINE CORRECTIONS ON PLANS
 SHT A2.
  
 2) ENGINERRS SHALL INDICATE THEIR
 LICENSE NUMBER ON EACH SHEET.
  
  