Plan Review Notes
Plan Review Notes For Permit 04120385
Permit Number 04120385
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-20 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} THE COUNTERTOP RECEPTACLE SPACING
 DOES NOT COMPLY WITH 210.52(C)(1) AND
 210.52(C)(3).
  
 3} PLEASE LIST ALL THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE.
 PER 210.11(C)(3).
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5} PLEASE SEE CHAPTER 34 FBC FOR
 ADDITIONAL REQUIREMENTS.INDICATE GFI AND
 SMOKE DETECTOR COMPLIANCE ON ELECTRICAL
 PLAN.
  
 6} RECEPTACLE SPACING IN THE BEDROOM
 DOES NOT APPEAR TO COMPLY WITH
 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW