| Plan Review Notes For Permit 04120385 |
| Permit Number |
04120385 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-20 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | | | | 1} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | 2} THE COUNTERTOP RECEPTACLE SPACING | | | DOES NOT COMPLY WITH 210.52(C)(1) AND | | | 210.52(C)(3). | | | | | | 3} PLEASE LIST ALL THE REQ'D DEDICATED | | | BATH(S) CIRCUIT(S) ON PANEL SCHEDULE. | | | PER 210.11(C)(3). | | | | | | 4} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 5} PLEASE SEE CHAPTER 34 FBC FOR | | | ADDITIONAL REQUIREMENTS.INDICATE GFI AND | | | SMOKE DETECTOR COMPLIANCE ON ELECTRICAL | | | PLAN. | | | | | | 6} RECEPTACLE SPACING IN THE BEDROOM | | | DOES NOT APPEAR TO COMPLY WITH | | | 210.52(A)(1). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|