Plan Review Notes
Plan Review Notes For Permit 04120363
Permit Number 04120363
Review Stop B
Sequence Number 1
Notes
Date Text
2004-12-20 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2-PROVIDE COMPLETE WALL SECTION THRU
 GARAGE BAY WINDOW. SPECIFY ALL
 FASTENERS. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 3-REVISE ROOF SHEATHING NOTE ON SHEET
 A3. ROOF ZONE 3 IS NOT ONLY AT 4
 CORNERS
 BUT AT ALL ROOF CORNERS. SEE FIGURE
 1606.2(C) FBC 2001.
  
 4-REVISE ATTIC LIVE LOAD SPECIFIED ON
 ROOF LOADS TABLE ON SHEET A3. SEE TABLE
 1604.1 FBC 2001.
  
 5-PROVIDE ONLY THE DETAILS THAT APPLY
 TO
 THIS JOB TO EXPEDITE REVIEW PROCESS.
  
 6-ROOF FRAMING PLAN AND ELEVATIONS
 DON'T
 SHOW THE CHIMNEY. REVISE AS REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 7-VERIFY THAT CHIMNEY UL LISTING AND
 SPECS ALLOW FLUE CAP TO HAVE ROOF ABOVE
 FOR PROPER FIREPLACE VENTILATION. THEN,
 REVISE DETAIL AS REQUIRED. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 8-PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL
 FOR (2 COPIES):
 A) ENTRY DOORS AS SHOWN ON PLANS.
 B) COMPLETE UL LISTING AND SPECS FOR
 FIREPLACE.
  
 9-AREA CALCULATIONS ON SHEET A1 DON'T
 ADD UP. REVISE AS REQUIRED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 10-OWES #2032.65 FOR LOW VALUATION AND
 RADON FEES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.