| 2004-12-20 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2-PROVIDE COMPLETE WALL SECTION THRU |
| | GARAGE BAY WINDOW. SPECIFY ALL |
| | FASTENERS. SECTION 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 3-REVISE ROOF SHEATHING NOTE ON SHEET |
| | A3. ROOF ZONE 3 IS NOT ONLY AT 4 |
| | CORNERS |
| | BUT AT ALL ROOF CORNERS. SEE FIGURE |
| | 1606.2(C) FBC 2001. |
| | |
| | 4-REVISE ATTIC LIVE LOAD SPECIFIED ON |
| | ROOF LOADS TABLE ON SHEET A3. SEE TABLE |
| | 1604.1 FBC 2001. |
| | |
| | 5-PROVIDE ONLY THE DETAILS THAT APPLY |
| | TO |
| | THIS JOB TO EXPEDITE REVIEW PROCESS. |
| | |
| | 6-ROOF FRAMING PLAN AND ELEVATIONS |
| | DON'T |
| | SHOW THE CHIMNEY. REVISE AS REQUIRED. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 7-VERIFY THAT CHIMNEY UL LISTING AND |
| | SPECS ALLOW FLUE CAP TO HAVE ROOF ABOVE |
| | FOR PROPER FIREPLACE VENTILATION. THEN, |
| | REVISE DETAIL AS REQUIRED. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 8-PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL |
| | FOR (2 COPIES): |
| | A) ENTRY DOORS AS SHOWN ON PLANS. |
| | B) COMPLETE UL LISTING AND SPECS FOR |
| | FIREPLACE. |
| | |
| | 9-AREA CALCULATIONS ON SHEET A1 DON'T |
| | ADD UP. REVISE AS REQUIRED. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 10-OWES #2032.65 FOR LOW VALUATION AND |
| | RADON FEES. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |