Text |
| 2006-07-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | |
| | |
| | |
| | |
| | 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER |
| | SHOWN IS NOT SHOWN ON THE GROUND FLOOR. |
| | WHERE DOES THIS RISER TERMINATE? PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | ***THIS SHEET HAS NOT BEEN REVISED AS |
| | REQUIRED IN THE PROVISO. |
| | |
| | 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO |
| | RISER 10 DOES NOT REFLECT THE FLOOR |
| | PLAN. PLEASE CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1. |
| | ***THIS SHEET HAS NOT BEEN REVISED AS |
| | REQUIRED IN THE PROVISO. |
| | |
| | 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT |
| | SHOWN ON THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | ***THIS SHEET HAS NOT BEEN REVISED AS |
| | REQUIRED IN THE PROVISO. |
| | |
| | 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING |
| | LAYOUT DOES NOT REFLECT RISERS 10A, 11, |
| | 11A AND 12 AS INDICATED. PLEASE |
| | CORRELATE RISERS AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | ***RESPONSE NOTED, BUT NO VENT FROM |
| | RISER #11 IS SHOWN ON THE FLOOR PLAN. |
| | |
| | 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS |
| | REQUIRED ON RISER 54A AT THE 5TH FLOOR |
| | OFFSET. SECTIONS 915.2 & 915.3. |
| | ***RESPONSE NOTED, BUT THE UPPER OFFSET |
| | VENT IS NOT SHOWN. SECTION 915.2. (ALSO |
| | SEE RISER #6 UPPER OFFSET VENT NOT |
| | SHOWN). |
| | |
| | 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN |
| | SHALL NOT TERMINATE IN THE PARKING |
| | GARAGE. SECTION 504.8.2. - EXPLAIN HOW |
| | DRAINING THE PTR DISCHARGE LINE INTO THE |
| | GARAGE PARKING MEETS THE REQUIREMENT FOR |
| | A SAFE DISCHARGE. SECTION 604.7.1. |
| | ***RESPONSE NOTED, BUT PAN DRAIN LINE |
| | STILL SHOWN DISCHARGING INTO THE PARKING |
| | GARAGE. |
| | |
| | *************REVISION NOTES************* |
| | |
| | 1. SHT P2.01 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101, 2003 |
| | CHAPTER 7 SECTION 7.1.3.2.1(6). |
| | |
| | 2. SHT P2.02 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). - PAN DRAIN TO GARAGE NOT |
| | APPROVED. SECTION 504.8.2. |
| | |
| | 3. SHT P2.03 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). - CLOUD AND NUMBER ALL |
| | REVISIONS. SECTION 104.2.1.3. |
| | |
| | 4. SHT P2.04 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE |
| | NOT APPROVED. SECTION 504.8.2. |
| | |
| | 5. SHT P2.06 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE |
| | NOT APPROVED. SECTION 504.8.2. |
| | |
| | 6. SHT P2.08 FLOOR DRAIN I EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR |
| | DRAIN. SECTION 901.2.1. |
| | |
| | 7. SHT P3.27 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). |
| | |
| | 8. SHT P330 2 FLOOR DRAINS IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6).- VENT REQUIRED FOR FLOOR |
| | DRAIN AT STAIRWELL #3. SECTION 901.2.1. |
| | |
| | 9. SHT P3.31 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). |
| | |
| | 10. SHT P3.36 FLOOR DRAIN IN EGRESS |
| | STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| | 7.1.3.2.1(6). |
| | |
| | 11. THE FOLLOWING SHEETS WERE APPROVED: |
| | P2.05, P2.07, P2.12, P2.17, P2.26, |
| | P2.27, P2.28, P2.33, P2.36, P2,39, |
| | P2.4O, P2.45, P2.51, P2.61, P3.00, |
| | P3.04, P3.16, P3.18, P3.19, P3.20, |
| | P3.21, P3.22, P3.23, P3.24, P3.25, |
| | P3.26, P3.28, P3.29, P3.32, P3.33, |
| | P3.34, P3.35, P3.37, P3.40, & P3.41 |
| | |
| | |
| | REVIEW BY KEN STEVENS |