| 2006-08-17 00:00:00 | REV'S FROM 6, 6A IN ELEC FOR REVIEW. | | | REV'S 6 AND 6A OK, | | | REDLINED , 3/4" CONDUIT TO FEED FOR POOL | | | LTS TOO SMALL FOR A TOTAL OF 4-#8'S | | | REDLINED ALUM CONDUCTORS FOR FEEDERS ARE | | | NOT PERMITTED SMALLER THAN #3. | | | NO ALUM EQUIPMENT GROUNDING CONDUCTORS. |
|