| Date |
Text |
| 2006-03-25 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: (FROM 1ST REVIEW) |
| | |
| | 12) SHT A4.41 KITCHEN SINK AND JUICE BAR |
| | SINK IN COMMON AREAS SHALL COMPLY WITH |
| | SECTION 11-4.24 AND ALL SUBSECTIONS. |
| | SUBMIT A DETAIL. RESPONSE NOTED, BUT NO |
| | DETAIL WAS FOUND. - THIS WILL BE A FIELD |
| | INSPECTOR APPROVAL. IF COMMON USE AREA |
| | IS AVAILABLE TO TENANTS AND SUESTS, ALL |
| | REQUIREMENTS OF SECTION 11-4.24 WILL BE |
| | ADHERED TO. - DETAIL SUBMITTED IS FOR |
| | THE DWELLING UNITS. SINKS INDICATED |
| | SHALL COMPLY AS REQUIRED IN SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| | 11-4.24.2 HEIGHT, 11-4.24.3 KNEE |
| | CLEARANCE, 11-4.24.4 SINK DEPTH, |
| | 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD |
| | APPROACH), 11-4.24.6 EXPOSED PIPES AND |
| | SURFACES, AND 11-4.24.7 FAUCETS. |
| | |
| | NEW COMMENTS GENERATED FROM CHANGES TO |
| | PLANS. 4/A: |
| | 1-4A. SHEET P2.37 MISSING FROM ONE SET |
| | OF PLANS. |
| | 2-4A. NEW SEAL REQUIRED FOR ENGINEER |
| | EFFECTIVE 1-1-06. SEE ATTACHED SHEET |
| | FROM THE FLORIDA BOARD OF PROFESSIONAL |
| | ENGINEERS. |
| | 3-4A. SHT P2.04, CHANGE 4.1 CONDENSATE |
| | DRAIN PIPING SHOWS EXTRA LINES TO UNITS |
| | 11 AND 12. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 4-4A. SHT P2.05 CHANGE 5.3 CONDENSATE |
| | DRAIN FOR A/C UNIT P1-5 NOT SHOWN ON SHT |
| | P2.61 AS NOTED. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 5-4A. SHT P2-06 CHANGE 6.4 PLEASE |
| | INDICATE WHAT IS DRAINING INTO THE 3" FD |
| | CONNECTED TO RWL'S 7 & 8. |
| | 6-4A. SHT P2.06 CHANGE 6.4 CONDENSATE |
| | DRAIN 28A DOES NOT CONNECT TO RISER C14, |
| | 15, 16, 24 & 26. RISER SHOWS 24A & 26A |
| | CONNECTING TO THIS RISER. PLEASE |
| | CORRELATE RISER AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER |
| | SHOWN IS NOT SHOWN ON THE GROUND FLOOR. |
| | WHERE DOES THIS RISER TERMINATE? PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO |
| | RISER 10 DOES NOT REFLECT THE FLOOR |
| | PLAN. PLEASE CORRELATE RISER AND FLOOR |
| | PLAN. SECTION 104.2.1. |
| | 9-4A. SHT P2.26 CHANGE 24.1 HORIZONTAL |
| | BRANCH SHALL NOT CONNECT WITHIN THE |
| | HORIZONTAL STACK OFFSET OR WITH 2 FEET |
| | ABOVE OR BELOW SUCH OFFSET. SECTION |
| | 711.2 |
| | 10-4A. SHT P2.27 CHANGE 25.1 NOT ALL |
| | VENT PIPING IS SHOWN ON THE FLOOR PLAN. |
| | SECTION 104.2.1. |
| | 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT |
| | SHOWN ON THE RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 12-4A. SHT P2.36 CHANGE 32.1 VENTING NOT |
| | SHOWN FOR BATH #2. SECTION 104.2.1. |
| | 13-4A. SHT 2.44 CHANGE 37.3 UNIT P2 |
| | PIPING DOES NOT REFLECT RISER 59. NO |
| | VENT CONNECTION FROM W/M TO L/SK AND |
| | FLOOR PLAN SHOWS THE RISER BEHIND THE |
| | LAUNDRY SINK. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING |
| | LAYOUT DOES NOT REFLECT RISERS 10A, 11, |
| | 11A AND 12 AS INDICATED. PLEASE |
| | CORRELATE RISERS AND FLOOR PLAN. SECTION |
| | 104.2.1. |
| | 15-4A. SHT P2.45 CHANGE 38.3 NOT ALL |
| | VENT PIPING WAS ADDED TO REFLECT THE |
| | RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 104.2.1. |
| | 16-4A. SHT P2.61 CHANGE 47.1 STORM |
| | RISERS6, 7 & 8, 9 & 10, AND DOWNSTREAM |
| | OF 4 & 5 SHOW 3" FLOOR DRAINS. PLEASE |
| | INDICATE WHAT IS DRAINING INTO THESE |
| | FD'S. SECTION 104.2.1. |
| | 17-4A. SHT P2.61 CHANGE 47.1 STORM |
| | PIPING DOWNSTREAM OF WHERE RWL 1 & RWL |
| | 11 TIE TOGETHER SHALL BE 12". 10" SHOWN. |
| | DOWNSTREAM OF THAT THE STORM DRAIN SHOWS |
| | 16" PIPE BUT IS SHOWN AS 15" ON THE |
| | RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 104.2.1. |
| | 18-4A. SHT P2.61 CHANGE 47.1 CONDENSATE |
| | LINE LEFT OF RWL 1, PLEASE INDICATE WHAT |
| | RISERS ARE BEING PICKED UP BY THE 3 |
| | LINES. NO INDICATION OF WHAT IS |
| | CONNECTING TO THESE LINES. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS |
| | REQUIRED ON RISER 54A AT THE 5TH FLOOR |
| | OFFSET. SECTIONS 915.2 & 915.3. |
| | 20-4A. SHT P3.22 NEW SHEET RISERS 28 & |
| | 84 LAV FOR 6TH FLOOR MISSING AND THE W/M |
| | IS ON THE WRONG STACK. CORRELATE RISER |
| | AND FLOOR PLAN. SECTION 104.2.1. |
| | 21-4A. SHT P3.24 VENT PIPING DOES NOT |
| | REFLECT THE ROOF VENT LAYOUTS. VENTING |
| | ALSO INDICATE "TO 31" WHEN THE VENTS ARE |
| | COMMING FROM 31. SUBMIT A RISER |
| | ISOMETRIC DIAGRAM FOR THE VENT PIPING |
| | SHOWING ALL PIPE SIZES, TOTAL DEVELOPED |
| | LENGTH AND INDICATE FIXTURE UNITS AS |
| | THEY ACCUMULATE IN THE VENT SYSTEM. |
| | TABLE 916.1 |
| | 22-4A. SHT P3.26 CHANGE 64.1 WATER |
| | CLOSET IS NOT VENTED AS CHANGED. SECTION |
| | 901.2.1. |
| | 23-4A. SHT P3.28 CHANGE 66.2SANITARY |
| | RISER 12 THRU 17 AND 51 DOES NOT REFLECT |
| | THE FLOOR PLAN WHERE IT CONNECTS TO THE |
| | BUILDING DRAIN. PLEASE CORRELATE RISER |
| | AND FLOOR PLAN, AND RECHECK THE FIXTURE |
| | UNITS AND PIPE SIZE. SECTION 104.2.1. |
| | 24-4A. SHT P3.28 CHANGE 66.5 A |
| | HORIZONTAL BRANCH SHALL NOT CONNECT |
| | WITHIN THE HORIZONTAL STACK OFFSET. |
| | SECTION 711.2. |
| | 25-4A. SHT P3.29 CHANGE 67.1 TABLE |
| | 710.1(1) 1/8"/FT SLOPE REQUIRED. |
| | INDICATE ON PLANS. (ALSO SEE SHT P3.28 |
| | 10 @ 2559FU). |
| | 26-4A. SHT P3.29 CHANGE 67.2 DOES NOT |
| | CONNECT TO THE BUILDING DRAIN IN THE |
| | CORRECT LOCATION. CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 27-4A. SHT P3.30 CHANGE 68.1 INDICATE |
| | SLOPE OF PIPE (1/8"/FT) FOR WHERE |
| | REQUIRED. TABLE 710.1(1). |
| | 28-4A. SHT P3.31 CHANGE 69.1 SHOW SLOPE |
| | AS 1/8"/FT WHERE REQUIRED. TABLE |
| | 710.1(1). |
| | 29-4A. SHT P3.31 RISER 54 5TH FLOOR W/M |
| | MISSING. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 104.2.1. |
| | 30-4A. SHT P3.32 CHANGE 70.1 INDICATE |
| | SLOPE AT 1/8"/FT AS REQUIRED PER TABLE |
| | 710.1(1). |
| | 31-4A. SHT P3.33 CHANGE 7.1 FIXTURE UNIT |
| | COUNT AT 8" TO READ 1407FU, NOT 140FU AS |
| | SHOWN. SECTION 104.2.1. |
| | 32-4A. SHT PP3.34 CHANGE 72.1 PIPE SIZE |
| | DOWNSTREAM OF RISERS 39/75 TO BE 5" |
| | 203FU OR INDICATE AS 1/4"/FT SLOPE PER |
| | TABLE 710.1(1). |
| | 33-4A. SHT P3.36 CHANGE 74.1 SHOW SLOPE |
| | OF PIPE IN BLDG DRAIN AS 1/8"/FT WHERE |
| | REQUIRED PER TABLE 710.1(1). |
| | 34-4A. SHT P3.36 BRANCH LINE DOWNSTREAM |
| | OF RISER 37 IS 291FU 5" IS REQUIRED. |
| | ALSO SEE BASE OF STACK. TABLE 710.1(1). |
| | - THE SIZE OF THE DRAINAGE PIPING SHALL |
| | NOT BE REDUCED IN SIZE IN THE DIRECTION |
| | OF FLOW. SEE DOWNSTREAM OF RISER 37 AND |
| | WHERE RISERS CONNECT TO THE BLDG DRAIN. |
| | SECTION 704.2. |
| | 35-4A. SHT P3.36 CHANGE 74.2 RISER 71 |
| | DOES NOT CONNECT TO RISER 33. PLEASE |
| | CLARIFY. SECTION 104.2.1. |
| | 36-4A. SHT P3.36 CHANGE 74.3 RISER 33 IS |
| | NOT SHOWN ON THIS SHEET. IT SHOULD BE |
| | INDICATED THAT THE VENT FROM THE EWC AND |
| | THE SINK CONNECT TO RISER 33. SECTION |
| | 104.2.1. |
| | 37-4A. SHT P3.37 CHANGE 75.1 PLEASE |
| | CORRECT PIPE SIZE AND SQUARE FOOTAGE FOR |
| | PIPE PRIOR TO AND AFTER RISERS RW1 AND |
| | RW11 CONNECT. SECTION 104.2.1. AND TABLE |
| | 1106.3. |
| | 38-4A SHT P3.37 CHANGE 75.2 RISER STATES |
| | "SEE P2.02 FOR CONT.", BUT NO PIPING |
| | SHOWN ON P2.02. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 39-4A SHT P3.40 CHANGE 78.1 SHOWS 1/4" |
| | CONDENSATE LINE. SHALL BE 1-1/4" AS |
| | SHOWN UPSTREAM. |
| | 40-4A SHT P3.41 CHANGE 79.1 SHOWS 1" |
| | CONDENSATE LINE. SHEE BE 1-1/2" AS SHOWN |
| | UPSTREAM. |
| | |
| | NEW COMMENTS: |
| | |
| | 1-E. SHT P3.21 RISER 26 DOES NOT REFLECT |
| | THE FLOOR PLAN. NO DRAINAGE LINE FROM |
| | KITCHEN SINK AND W/M SHOWN ON THE FLOOR |
| | PLAN. PLEASE CORRELATE. SECTION 104.2.1. |
| | 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN |
| | SHALL NOT TERMINATE IN THE PARKING |
| | GARAGE. SECTION 504.8.2. - EXPLAIN HOW |
| | DRAINING THE PTR DISCHARGE LINE INTO THE |
| | GARAGE PARKING MEETS THE REQUIREMENT FOR |
| | A SAFE DISCHARGE. SECTION 604.7.1 |
| | 3-E SHT P2.40 (NEW SHEET) NO DRAINAGE |
| | SHOWN FOR THE W/M, L/SINK, OR KITCHEN |
| | SINK. PLEASE CORRELATE WITH RISER |
| | DIAGRAM. SECTION 104.2.1. |
| | 4-E SHTS P2.59 AND P2.60 PLEASE SHOW |
| | TOTAL DEVELOPED LENGTH AND TOTAL FIXTURE |
| | UNITS FOR COMBINED VENTS 31 THRU 45, 46 |
| | THRU 50, 65 & 78. INDICATE ALL VENT PIPE |
| | SIZES. TABLE 916.1 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |